CE M11- FB P. X X X E A RTH LE A K AG E MON ITOR
M A N UA L
—
Technical data
Supply voltage
24 V DC (+30 % ... -20 %)
(19.2 ... 31.2 V DC) including ripple
Supply current
Max. 0.5 mA
Total device dissipation
Max. 125 mW
Motor voltage
Max. 1000 V AC, isolated wires have to be used
Selectable earth fault
current thresholds
CEM11-FBP.20 80
1)
, 300, 550, 750, 1000, 1200, 1500, 1700 mA
CEM11-FBP.35 100
1)
, 500, 1000, 1400, 2000, 2400, 3000, 3400 mA
CEM11-FBP.60 120
1)
, 1000, 2000, 2800, 4000, 4800, 6000, 6800 mA
CEM11-FBP.120 240
1)
, 2000, 4000, 5600, 8000, 9600, 12000, 13600 mA
Tripping and tripping time
If the earth fault current is above the adjusted threshold the control device (e.g. UMC100.3 or
PLC) is responsible to switch off the motor within the specified tripping time (e.g. 1 s).
Earth fault detection time of CEM11-FBP.xxx is about 25 ms. UMC100.3 or PLC should use an
additional delay time to ignore short disturbances.
Max. inaccuracy of the threshold level
+/- 10 %
+/- 30 % for the currents marked with
1)
Output signal
Earth fault current lower
than threshold value
Signal: output switches to + 24 V DC (“closed contact”)
Max. voltage drop: 4.1 V DC
Max. load: 30 mA
Earth fault current
higher than
threshold value
Signal: output opens (“open contact”)
Max. output current: 0.5 mA
Max. output low voltage 1.9 V DC
Connecting capacity
Solid or stranded
0.75 - 1.5 mm
2
/ 18 - 16 AWG
Stripping length
5 … 6 mm / 0.2 … 0.24 inch
Cable length
10 m shielded or unshielded
Mounting
CEM11-FBP.xxx On DIN rail (IEC/EN 60715, 35 mm) or with screws, in each case with the provided accessories.
CEM11-FBP.120
Only with screws
Mounting position
No restrictions
Dimensions
See "Dimensional drawings"
Net weight
CEM11-FBP.20 130 g
CEM11-FBP.35 200 g
CEM11-FBP.60 330 g
CEM11-FBP.120 940 g
Pollution degree
Terminals
3
Degree of protection
IP20
Temperature range
Storage
- 40 ... + 75 °C
Operation
0 ... + 60 °C
Operation altitude above sea level
Up to 5000 m
Approvals
CE, cUL
2)
1)
Lowest values have higher inaccuracy
2)
Device is not suitable to be used as a substitute for a GFCI (Ground-Fault Circuit-Interrupters) or a Listed Ground Fault Sensing an Relaying Equipment (UL)