CBXi IP Controller |
CBXi Operation
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
65
MAN
01
41
re
v 2
3
Service Port (Micro USB)
Ethernet Ports
Indicator LEDs
(for LED signals see
Output Override (
CBXi-8R8-H
only
)
Bottom position: Off - outputs forced off.
Centre position:
Auto - outputs are controlled by strategy.
Top position: Manual - for digital outputs, the output is forced on. For analog
outputs the knob setting controls the output value.
Note
: Manual position is supervised, i.e. the
strategy
is aware of the manual value.
Push buttons
Reset IP/Password : while the controller is
running
, press SW
1
until the LED lights
up, then release SW1.
Full factory reset :
while the controller is
booting
hold SW1 until the LED lights up,
then release SW1.
Restart the controller : while the controller is
running
, press SW2 until the LED lights up.
, then release SW2.
Inter-module connection sockets
To join the
FLX bus
, place the devices side-by-side and place the
FLX bus
connector
into the two adjacent sockets at once.
The end device on a
FLX bus
(either a
FLX
device or the
CBXi
itself) must have a
terminator inserted into its interconnector socket. One terminator is shipped
with each
CBXi-8R8(-H)
device.
CBXi INDICATOR LED SIGNALS
Off
On
Slow Blink
Fast blink
Red LED
(Power)
Power is off
Power is on
____ Unit Rebooting ____
Green LED
(Status)
Unit is not
running
Strategy Loaded
but no network
connectivity
Strategy Loaded and
device communicating
on network
No Strategy
loaded
Yellow LED
(FLX)
FLX bus
comms are
ok
No FLX bus comms
FLX bus address clash
FLX bus
comms error
During firmware upgrade the Yellow LED will remain on while the strategy/comms section reboots, and
then the LEDs will rotate Red-Green-Yellow while the IO section reboots.
Note
: During typical operation, the Red LED should be on, the Green LED should