OPERATION OF THE DISPLAY

 

 

 

USER & ENGINEERING MODES

 

User Mode 

If the Controller 

Strategy

 has been configured to permit it, the 

user can adjust the temperature setpoint or occupancy status. 

Enter the User Mode by pressing any button until the 

temperature setpoint is displayed on the second line with a 

flashing unit symbol 

 

When in 

User Mode

, press the up button 

 or down button 

 to 

adjust the setpoint value by the span defined in the  Controller 
configuration until the desired temperature setpoint is displayed. 

 

When in 

User Mode

, the right button 

  can also be used to request 

the 

Strategy

 to override the 

schedule

 and force occupancy mode. 

Permit  Occupancy  Override

”  must  be  enabled  in  the  controller 

configuration. 

Engineering Mode 

In 

Engineering Mode

, the keypad can be used as a 

commissioning tool; adjusting preconfigured parameters within 

the controller strategy. To enter 

Engineering Mode

 

Hold  both  the  up  button 

      and  down  button 

  for  3 

seconds,  until  the  text PASS is displayed  on the top line (large 
text). 

 

Enter the password (a series of digits) using the left 

 and right 

  buttons to select each digit, and then the up 

 and down 

 buttons to increment or decrement the selected digit. The 

default  password  is  9999,  which  can  be  changed  over  the 
network. 

 

When the password is complete, press and hold the right button 

 for 3 seconds. If the password is accepted, the Engineering 

menu will be displayed. 

 

 

a

 

1st Line (large digits)

 

In User Mode, this displays the current 
temperature reading

 

In Engineering Mode, this displays menu text

 

 

2nd Line (small digits)

 

In User Mode, this displays one of the following:

 

• 

Humidity (CBT-STAT-H)

 

• 

Temperature Setpoint (CBT-STAT)

 

In Engineering Mode, this displays menu text

 

 

OPERATION MODE INDICATORS

 

 

 

 

Indicates that the controller is 

operating in “heating” mode

 

 

 

 

Indicates that the controller is 

operating in “cooling” mode

 

 

 

 

Indicates that the controller 
strategy is currently operating 

in “occupancy” mode

 

 

 

 

Indicates whether the occupancy 
mode is controlled by a time 
schedule, or is manually overridden

 

 

 

 

Indicated that an alarm state is detected 
in the controller strategy

 

 

 

 

Indicates that the fan is operating

 

 

 

 

Indicates that the keypad is operating in 
Engineering Mode

 

 

KEYPAD 

 

 

Left Button

 

User Mode: No function

 

Engineering Mode: Change menu page

 

 

 

Up Button

 

User Mode: Increase setpoint

 

Engineering Mode: Change menu line, 
increase value

 

 

 

Right Button

 

User Mode: Toggle occupancy mode

 

(if “Permit Occupancy Override” is 

enabled)

 

Engineering Mode: Change menu page, 
start parameter editing, accept changes

 

 

 

Down Button

 

User Mode: Decrease setpoint

 

Engineering Mode: Change menu line, 
decrease value

 

 

 

 

 

 
 
 
 
 
 
 

 