ABB CA-26 Instruction Leaflet Download Page 4

41-337.31B

4

required to close the relay contacts, expressed in
percent of the total restraint current, varies with the
magnitude of the restraint current. The relay sensi-
tivity is high, corresponding to a low percentage
ratio, at light currents, and its sensitivity is low, cor-
responding to high percentage unbalance, at high
currents. The relay is made sensitive at low cur-
rents in order to detect light internal faults on the
bus being protected. At the same time, however, its
reduced sensitivity at the higher currents allows the
various current transformers involved to depart
from their true ratio to a large extent without caus-
ing false tripping of the relay for external faults.

The variable percentage characteristics are partic-
ularly advantageous when severe saturation of cur-
rent transformers is caused by the dc component of
asymmetrical short circuits. In the case of buses
located close to generating stations where the dc
components decay slowly, the breakdown in ratio of
the current transformers will be much greater than
would ever be expected from a consideration of the
usual ratio curves of the current transformers
involved.

The time of operation of the relay is shown in Fig-
ure 4.

The main contacts will safely close 30 amperes at
250 volts dc and the seal-in contacts of the indicat-
ing contactor switch will safely carry this current
long enough to trip a circuit breaker.

The indicating contactor switch has two taps that
provide a pick-up setting of 0.2 or 2 amperes. To
change taps requires connecting the lead located in
front of the tap block to the desired setting by
means of a screw connection.

4.2.

Trip Circuit Constants

Indicating Contactor Switch (ICS)

0.2 amp rating

8.5 ohms dc

1.0 amp rating

0.37 ohms dc

2.0 amp rating

0.10 ohms dc

ENERGY REQUIREMENTS

Burden of each restraint coil at 5 amperes

VOLT AMPERES

POWER FACTOR

.75

.7

Continuous Rating

14 amperes

1 second rating

460 amperes

Burden of operating Circuit

VOLT AMPERES

VARIABLE (See

 

Figure 5)

Continuous rating 8 amperes

1 second rating 280 amperes

4.3.

Connections

4.3.1. CA-16

To determine the ac connections, identify each pri-
mary circuit as either a “source” or “feeder”. As
defined here, a feeder contributes only a small por-
tion of the total fault-current contribution for a bus
fault. Otherwise, the circuit is a source. Next lump a
number of feeders into a “feeder group” by paralleling
feeder ct’s, taking the precaution that each feeder
group has less than 14 amperes load current
(restraint coil continuous rating). Also each feeder
group should not contribute more than 10% of the
total phase or ground-fault current for a bus fault if
Figure 7 is to be used.

Connect per Figure 6 with three or four bus “circuit.”
The term “circuit” refers to a source or to a feeder
group. For example, assume a bus consisting of 2
sources and 6 feeders. Further, assume that the
feeders are lumped into 2 feeder groups. The bus
now reduces to four circuits

If the bus reduces to more than four circuits, parallel
source-circuit ct’s or source-and feeder circuit ct’s
until only four circuits remain. Then connect these
four sets of ct’s to the relays per Figure 6. The excep-
tion to this rule occurs when the application consists
of three feeder groups. Then Figure 7 applies.

With 3 feeder groups and more than 3 sources, paral-
lel source ct’s until the application reduces to 6 cir-
cuits; then, connect to the relays per Figure 7.

4.4.

Setting Calculations

No calculations are required to set the CA-16.

4.5.

Setting The Relay

No settings are required on the CA-16 relay.

5.0

INSTALLATION

The relays should be mounted on switchboard panels
or their equivalent in a location free from dirt, moisture,
excessive vibration and heat. Mount the relay verti-
cally by means of the four mounting holes on the
flange for the semi-flush type FT case. The mounting
screws may be utilized for grounding the relay. Exter-
nal toothed washers are provided for use in the loca-
tions shown on the outline and drilling plan to facilitate
making a good electrical connection between the relay
case, its mounting screws and the relay panel. Ground
Wires are affixed to the mounting screws as required
for poorly grounded or insulating panels. Other electri-
cal connections may be made directly to the terminals
by means of screws for steel panel mounting.

Courtesy of NationalSwitchgear.com

Summary of Contents for CA-26

Page 1: ...fety classification of the electric equipment and systems in nuclear power generating stations that are essential to emergency shutdown of the reactor containment isolation cooling of the reac tor and heat removal from the containment and reac tor or otherwise are essential in preventing significant release of radioactive material to the environment The current transformers should not saturate whe...

Page 2: ...41 337 31B 2 Figure 1 CA 16 Front View Figure 2 CA 16 Rear View Courtesy of NationalSwitchgear com ...

Page 3: ...de rod by two small nuts Its position determines the pick up current of the element The auto transformer is designed to saturate at high values of current to limit the amount of current to the contactor switch 2 3 1 Indicating Contactor Switch Unit ICS The dc indicating contactor switch is a small clapper type device A magnetic armature to which leaf spring mounted contacts are attached is attract...

Page 4: ... CA 16 To determine the ac connections identify each pri mary circuit as either a source or feeder As defined here a feeder contributes only a small por tion of the total fault current contribution for a bus fault Otherwise the circuit is a source Next lump a number of feeders into a feeder group by paralleling feeder ct s taking the precaution that each feeder group has less than 14 amperes load ...

Page 5: ...eres 6 2 Routine Maintenance All contacts should be periodically cleaned A contact burnisher is recommended for this purpose S 182A836H01 The use of abrasive material for cleaning contacts is not recommended because of the danger of embedding small particles in the face of the soft silver and thus impairing the contact 7 0 CALIBRATION Use the following procedure for calibrating the relay if the re...

Page 6: ...d 15 Operate the moving element by hand and allow the current to hold the moving contact disc against the stationary contacts Now screw up the core screw slowly This causes the plunger to move up compressing the spring until a point of maximum deflection is reached Further upward motion will cause the plunger to drop part way out of the coil thus diminishing the spring pressure on the contacts By ...

Page 7: ...41 337 31B 7 This Page Reserved for Notes Courtesy of NationalSwitchgear com ...

Page 8: ...41 337 31B 8 Figure 3 Internal Schematic of the Type CA 16 Bus Relay Sub 1 3532A95 Courtesy of NationalSwitchgear com ...

Page 9: ...41 337 31B 9 Figure 4 Typical Time Curves of the CA 16 Differential Relay Sub 1 537956 Courtesy of NationalSwitchgear com ...

Page 10: ...41 337 31B 10 Figure 5 Typical Burden Characteristics of the Types CA 16 and CA 26 Relays Curve 537957 Courtesy of NationalSwitchgear com ...

Page 11: ...41 337 31B 11 Figure 6 External Schematic of One Set of Type CA 16 Relays for the Protection of a Three and Four Circuit Bus Sub 5 187A424 Courtesy of NationalSwitchgear com ...

Page 12: ...41 337 31B 12 Figure 7 External Schematic of the Type CA 16 Relays for Protection of Six Circuit Bus with Three Feeder Groups Sub 5 187A425 Courtesy of NationalSwitchgear com ...

Page 13: ...41 337 31B 13 Figure 8 Diagram of Test Connections for the CA 16 Relay Sub 4 187A426 Courtesy of NationalSwitchgear com ...

Page 14: ...41 337 31B 14 Figure 9 Percentage Slope Curve of the CA 16 Relay with One Restraint Winding Sub 1 849A450 Courtesy of NationalSwitchgear com ...

Page 15: ...41 337 31B 15 Figure 10 Percentage Slope Curve of the CA 16 Relay with Six Restraint Windings in Series Sub 2 849A343 Courtesy of NationalSwitchgear com ...

Page 16: ...oral Ridge Drive Coral Springs Florida 33065 TEL 954 752 6700 FAX 954 345 5329 visit our website at www abbus com papd 41 337 31B Figure 11 Outline and Drilling for the CA 16 Relay in FT 32 Case Sub 1 3519A69 Courtesy of NationalSwitchgear com ...

Reviews: