45 x 45mm
+0.5 –0.0
CAUTION:
Turn off all power. Remove instrument by gripping the sides of the
front panel and pulling the instrument out of its housing. Note its orientation.
Panel-Mounting
The mounting panel must be rigid and may be up to 6.0mm
(0.25 inches) thick. The cut-out required for the instrument is
shown on the right. Instruments may be mounted side-by-side
in a multiple installation for which the cut-out width (for n
instruments) is (48n-4)mm or (1.89n-0.16)inches.
Rear Terminal Wiring
Note: At first power-up the message
is displayed, as
described in section 8 of this manual. Access to other menus is denied
until configuration mode is completed
Select mode is used to access the configuration and operation menu functions.
It can be accessed at any time by holding down and pressing .
Once in select mode, press or to select the required mode. An unlock code is
required to prevent unauthorised entry to Configuration, Setup & Automatic Tuning modes.
Press or to enter the correct code number, then press to proceed.
Mode
Upper
Display
Lower
Display
Description
Default Unlock
Codes
Operator
Normal instrument operation.
None
Set Up
Tailor settings to the application.
Configuration
Configures the instrument for use.
Product Info
Check manufacturing information.
None
Auto-Tuning
Invoke Pre-Tune or Self-Tune.
Note: The instrument will always return automatically to Operator mode if there is no
key activity for 2 minutes.
First select Configuration mode from Select mode (refer to section 2).
Press to scroll through the parameters, then press or to set the required value.
To accept a change must be pressed, otherwise parameter will revert to previous value.
To exit from Configuration mode, hold down and press , to return to Select mode.
Note: Parameters displayed depends on how instrument has been configured.
Parameters marked * are repeated in Setup Mode.
Parameter
Lower
Display
Upper
Display
Adjustment range
Default
Input Range/Type
See following table for possible codes
J T/C
Scale Range
Upper Limit
Scale Range Lower Limit +100 to Range Max Range max
(Lin=1000)
Scale Range
Lower Limit
Range Min. to Scale Range Upper Limit -100
Range min
(Linear=0)
Decimal point
position
0=XXXX, 1=XXX.X, 2=XX.XX, 3=X.XXX
(non-temperature ranges only)
1
Primary (heat) only
Control Type
Primary & Secondary (heat/cool)
Reverse Acting
Primary Output
Control Action
Direct Acting
Process High Alarm
Process Low Alarm
Deviation Alarm
Band Alarm
Alarm 1Type
No alarm
High Alm 1 value*
Range Max.
Low Alm 1 value*
Range Min. to Range Max
in display units
Range Min.
Band Alm 1 value*
1 LSD to span from setpoint in display units
Dev. Alm 1 value*
+/- Span from setpoint in display units
Alm 1 Hysteresis*
1 LSD to full span in display units
Process High Alarm
Process Low Alarm
Deviation Alarm
Band Alarm
Alarm 2 Type
No alarm
High Alm 2 value*
Range Max.
Low Alm 2 value*
Range Min. to Range Max
in display units
Range Min.
Band Alm 2 value*
1 LSD to span from setpoint in display units
Dev. Alm 2 Value*
+/- Span from setpoint in display units
Alm 2 Hysteresis*
1 LSD to full span in display units
Loop Alarm
(disabled) or
(enabled)
Loop Alarm Time*
1 sec to 99 mins. 59secs
(only applies if primary proportional band = 0)
.
No alarms Inhibited
Alarm 1 inhibited
Alarm 2 inhibited
Alarm Inhibit
Alarm 1 and alarm 2 inhibited
Parameter
Lower
Display
Upper
Display
Adjustment range
Default
Primary (Heat) Power
Secondary (Cool) Power
Alarm 1, Direct
Alarm 1, Reverse
Alarm 2, Direct
Alarm 2, Reverse
Loop Alarm, Direct
Loop Alarm, Reverse
Logical Alarm 1 OR 2, Direct
Logical Alarm 1 OR 2, Reverse
Logical Alarm 1 AND 2, Direct
Output 1 Usage
Logical Alarm 1 AND 2, Reverse
Primary (Heat) Power
Secondary (Cool) Power
Alarm 1, Direct
Alarm 1, Reverse
Alarm 2, Direct
Alarm 2, Reverse
Loop Alarm, Direct
Loop Alarm, Reverse
Logical Alarm 1 OR 2, Direct
Logical Alarm 1 OR 2, Reverse
Logical Alarm 1 AND 2, Direct
Output 2 Usage
Logical Alarm 1 AND 2, Reverse
Display Strategy
,
,
,
,
or
(refer to section 7)
Config Lock Code
0 to 9999
Input Ranges and Types
(See Configuration Mode Parameter
)
Code
Input Type & Range
Code
Input Type & Range
Code
Input Type & Range
bC
bC
bC
bC
B: 100 – 1824 ºC
L
LL
L
.
C
C
C
C
L: 0.0 – 537.7 ºC
bF
bF
bF
bF
B: 211 – 3315 ºF
L
LL
L
.
F
F
F
F
L: 32.0 – 999.9 ºF
P24F
P24F
P24F
P24F
PtRh20% vs 40%:
32 – 3362 ºF
CC
CC
CC
CC
C: 0 – 2320 ºC
NC
NC
NC
NC
N: 0 – 1399 ºC
PTC
PTC
PTC
PTC
Pt100: -199 – 800 ºC
CF
CF
CF
CF
C: 32 – 4208 ºF
NF
NF
NF
NF
N: 32 – 2551 ºF
PtF
PtF
PtF
PtF
Pt100: -328 – 1472 ºF
JC
JC
JC
JC
J: -200 – 1200 ºC
rC
rC
rC
rC
R: 0 – 1759 ºC
Pt
Pt
Pt
Pt
.
C
C
C
C
Pt100: -128.8 – 537.7 ºC
JF
JF
JF
JF
J: -328 – 2192 ºF
rF
rF
rF
rF
R: 32 – 3198 ºF
Pt
Pt
Pt
Pt
.
F
F
F
F
Pt100: -199.9 – 999.9 ºF
j
j
j
j
.
C
C
C
C
J: -128.8 – 537.7 ºC
SC
SC
SC
SC
S: 0 – 1762 ºC
0 – 20 mA DC
j
j
j
j
.
F
F
F
F
J: -199.9 – 999.9 ºF
SF
SF
SF
SF
S: 32 – 3204 ºF
4 – 20 mA DC
KC
KC
KC
KC
K: -240 – 1373 ºC
tC
tC
tC
tC
T: -240 – 400 ºC
0 – 50 mV DC
KF
KF
KF
KF
K: -400 – 2503 ºF
tF
tF
tF
tF
T: -400 – 752 ºF
10 – 50 mV DC
k
k
k
k
.
C
C
C
C
K: -128.8 – 537.7 ºC
t.C
t.C
t.C
t.C
T: -128.8 – 400.0 ºC
0 – 5 V DC
K
K
K
K
.
F
F
F
F
K: -199.9 – 999.9 ºF
t.F
t.F
t.F
t.F
T: -199.9 – 752.0 ºF
1 – 5 V DC
LC
LC
LC
LC
L: 0 – 762 ºC
0 – 10 V DC
LF
LF
LF
LF
L: 32 – 1403 ºF
P24C
P24C
P24C
P24C
PtRh20% vs 40%:
0 – 1850 ºC
2 – 10 V DC
CAUTION:
Do not remove the panel gasket; it is a seal against dust and
moisture.
CAUTION:
Installation and configuration should be performed only by
personnel who are technically competent to do so. Local Regulations regarding
electrical installation & safety must be observed.
1. INSTALLATION
C50 1/16-DIN PROCESS CONTROLLER
CONCISE PRODUCT MANUAL – IM/C50
Hold instrument firmly in position
(apply pressure to bezel only)
Mounting Panel
Instrument Housing
Ratchets
Gasket
Slide mounting clamp over the
instrument housing towards rear face
of mounting panel until the tongues
engage in ratchets and instrument is
clamped in position.
2. SELECT MODE
3. CONFIGURATION MODE
CAUTION
: Check information label on
housing for correct operating voltage
before connecting supply to Power Input
Fuse: 100 – 240V ac – 1amp anti-surge
NOTE: Option 2 is only available on
model C50K-2110-00.
USE COPPER CONDUCTORS
(EXCEPT FOR T/C INPUT)
Single Strand wire gauge:
Max 1.2mm (18SWG)