OPERATING LEVEL
Control Set Point
The set point in use is displayed (Local, Remote or Dual).
If the Local or Dual set point is displayed it can be adjusted
using the
and
switches, providing
Set Point Adjust
Enable
is set to
YES
– see
Section 4.2 of the Programming
Guide,
Set Points Page
.
Control Output Value (0 to 100%).
To adjust the output value manually: select Manual control
mode using the
switch ('M' l.e.d. is illuminated) and
then use the
and
switches to set the required value
Manual Reset (0 to 100%).
This frame is not displayed if an
Integral Action Time
is set
or
Manual Reset Adjust Enable
is set to
OFF
– see Section
7.2,
Control Page
.
Use the
and
switches to set a value which
eliminates any offset from the set point.
Temperature Units
This frame is not displayed if the
Display Units
parameter is
set to
NONE
– see
Section 4.8 of the Programming Guide
Set Up Display Page
.
Set Point Type Selection – Fig. 5.1 (previous page)
Use the
switch to view the various set point values. If the
difference is too great, press the
switch and return to the
Control Set Point
frame and adjust the Local set point to obtain
an acceptable difference. The Local set point tracks the
Remote set point when the Remote set point is selected,
providing
Remote Set Point Tracking Enable
is set to
YES
– see
Section 4.2 of the Programming Guide,
Set Points Page
.
Remote Set Point Ratio
The remote set point input (in engineering units) is
multiplied by the ratio to obtain the control set point value, i.e.
Remote Set Point Value
=
Input x Ratio + Bias
Use the
and the
switches to set the ratio required,
between 0.010 and 9.999 in 0.001 increments
Remote Set Point Bias
The bias value is added to the remote set point value (see
previous frame) Use the
and the
switches to set
the bias required. The bias can be set to either a positive or
negative value (in engineering units).
100.3
OP 50.0
100.3
r50.0
100.3
110.5
100.3
dEG F
LOCAL
110.5
LOCAL
bALNCE
rEMOtE
dUAL
or
rAtIO
1.000
bIAS
0.0
100.3
110.3
Process
Variable
5.2
Operating Page Displays
5.2.1
Time Proportioning and Analog Control