Summary of Contents for BL-1

Page 1: ...plications However the drop across a portion of the protected circuit such as the interpole field win ding of a machine sometimes can be utilized as a source of energy for the relay CONSTRUCTION AND OPERATION The single element type BL 1 relay consists of a heater unit an instantaneous overcurrent unit 0 two operation indicators and a contactor switch Figures 1 3 The double element type BL 1 relay...

Page 2: ...Fig 1 Type BL 1 Single Unit Relay without case Front View 2 ...

Page 3: ...I L 41 553 1G Fig 2 Type BL 1 Double Unit Relay without case Front View 3 Courtesy of NationalSwitchgear com ...

Page 4: ... currents of short duration The reactor should be removed from the circuit for dc application This is readily accomplished by removing the heavier lead from the two left hand terminals of each thermal unit enclosure of the internal spring will cause it to res pond more slowly than the external spring and a temporary change in contact position would result from a large and rapid change in ambient t...

Page 5: ... is a small solenoid type switch A cylindrical plunger with a silver disc mounted on its lower end moves in the core of the solenoid As the plunger travels up ward the disc bridges three stationary contacts The coil is in series with the main contacts of the relay and with the trip coil of the breaker When the relay contacts close the coil becomes energized and closes the switch contacts This shun...

Page 6: ...TACT REACHES FINAL POSITION FOR INITIAL STEADY LOAD INDICATED BELOW ZERO CURRENT INTERNAL TEMP AT APPROX AMBIENT TEMP 70 OF 3 5 AMPS 100 OF 3 5 AMPS V 1 5 1 1 1 1 l i I I I I 1 1 HT V 1 1 1 I I V i T u I I i I l I I I 1 r I I 1 1 X m 9 v 8 V XT T 7 m 6 V p a 5 i m A 1 m X 4 X p jz H t PI A 3 T X7 i V x x 2 I m r r f i 1 i s u s I 1 1 1 1 L 1 i I I I I I I i K J 1 i I i I I I U 1 I I i I k I i I 1 ...

Page 7: ...OAD APPLIED AFTER MOVING CONTACT REACHES FINAL POSITION FOR INITIAL STEADY LOAD INDICATED BELOW ZERO CURRENT INTERNAL TEMP AT APPROX AMBIENT TEMP 70 OF 5 AMPS 100 OF 5 AMPS l T T i i i V I M V I 1 v J jOk X 9 8 PI 7 J 6 I z4 v 5 7 5 fK 5 V 4 I X 3 Tx X X I iz i ri w i ES i 2 v r 7 i_L l v L C 1 n f LLU i A 1 1 1 1 I 093 MIN AT 1000 L s i i 1 100 200 300 400 500 600 700 800 900 1000 PERCENT OF POIN...

Page 8: ... I I i I 1 X T j yY T V 4 9 rr 8 is 3 FOR 2 75 AMP SETTING FOR 3 75 AMP SETTING WHEN STARTING FROM 100J OF FULL LOAD CURRENT 6 51 5 5 Y rt Y 5 Y 5r V L 5 1 X Y T j 3 r i K IT 2 1 I i l J i 075 MIN AT 1000J 1 r 100 200 300 400 500 600 700 800 900 1000 PERCENT OF FULL LOAD CURRENT 396063 Curve Fig 7 Current T ime Curves for Special Applications of the Type BL 1 Relay covering Range of F ull Load Cur...

Page 9: ...pe BL 1 Relay Covering Range of Fufl Load Currents from 4 0 to 5 0 Amperes Contact Settings Determined by Test for 15 Minute Delay with 125 Load Occurring after Moving Contact reaches Final Position for Steady Full Load Shorting Link Closed 9 Courtesy of NationalSwitchgear com ...

Page 10: ...Fig 9 Contact Opening and Reset Time Curves for the Type BL 1 Reioy for Fult Load Settings of 2 5 to 3 5 Amperes os marked on Dial Shorting Link Open 10 Courtesy of NationalSwitchgear com ...

Page 11: ...L 41 553 1G Contact Opening and Reset Time Curves for the Type BL 1 Relay for Full Load Settings of 3 75 to 5 0 Amperes as marked on Dial Shorting Link Closed Fig 10 11 Courtesy of NationalSwitchgear com ...

Page 12: ... ampere steps and when the scale pointer is set to one of the indicated current values the relay contacts will close in ap proximately 60 minutes if the current increases to 125 percent of the full load value after the full load current has been flowing long enough for the temperature rise to reach a constant value These curves represent the primary performance re quirements of the type BL 1 relay...

Page 13: ...of current that will ultimately close the relay contacts but variables such as friction and dis crepancies in calibration prevent precise location of the asymptotic value However after making some allowance for such variables a value of 118 of full load current can be considered as the max imum current that will not produce eventual clos ing of the relay contacts when settings are made as describe...

Page 14: ...supplied in the type BL 1 relay will pick up at 1 0 ampere direct current For detail information on the FT case refer to I L 41 076 SETTINGS CONTACT RATINGS There are two settings to be made on the relay They are as follows Control Capacity Will Break Control Voltage In Amperes Will Close Unit 1 INSTANTANEOUS UNIT Set the element for a pick up current slightly above the maximum current which the a...

Page 15: ...lower right posi tion Close switch S1 and pass sufficient dc current through the trip circuit to close the contacts of the ICS This value of current should not be greater than the particular ICS nameplate rating The in dicator target should drop freely Repeat above except to pass 85 of ICS nameplate rating current Contacts should not pick up and target should not drop Open switch S1 when checking ...

Page 16: ...roximately 16 CONTACTOR SWITCH Adjust the stationary core of the switch for a clearance between the stationary core and the moving core of l 64 when the switch is picked up This can be done by turning the relay up side down or by disconnecting the switch and turning it up side down Then screw up the core screw until the moving core starts rotating Now back off the core screw until the moving core ...

Page 17: ...minimize factors which would introduce calibra tion errors The test current should be interrupted as soon as the contacts close in order to avoid possible damage to the heaters particularly when testing at high values of overload RENEWAL PARTS Repair work can be done most satisfactorily at the factory However interchangeable parts can be furnished to the customers who are equipped for doing repair...

Page 18: ... 14 30 _ 5 375 36 53 4 0I6 397 250 _ 6 35 0 f 1 031 f 1 031 4 1 031 t 1 031 H 26 19 26 19 26 19 26 19 1 190 32 SCREW 375 1 344 SPACERS FOR 34 14 THIN PANELS 9 53 R PANEL CASE 1 r A 5 16 18 SCREW FOR THICK PANELS USE 5 16 18 STUDS INTERNAL EXTERNAL TOOTHED WASHERS 190 32 SCREW FOR THICK PANELS USE 190 32 STUDS 594 15 09 1 0 25 4 Li nt 5A 77 3 9 i 1 813 i 2 0 i 46 05 i 50 8 i IOV 2 4 6 8 1 V 516 13 ...