ABB AWT210 Manual Download Page 8

8

AW T 210

  H A R T  2- W I R E  T R A N SM I T T ER  |  CO M/AW T 2 10/H A R T- EN  R E V.  B

… 4  Installation

Multi-drop mode (digital) signal and power wiring (loop current mode enabled)

Refer to Figure 3 for a typical wiring configuration for multi-
drop installations.  In the multi-drop mode of operation, the 
analog 4 to 20 mA is not used.  Instead the transmitter draws a 
constant 3.6 mA of current to maintain operation.

•  Do not connect secondary communication device directly 

across the power supply.

•  Add 1 V DC to all minimum supply voltage values if using the 

TEST connections.

•  The maximum number of transmitters is 63.

+

+

+– +–

+– +–

System power supply

High impedance 

controller, recorder  

or control system

HART compatible hand-

held terminal (secondary 

communication device)

250 

ohms

Transmitter 1

Transmitter n

Figure 3  Digital mode wiring diagram 

In the multi-drop mode, the process variable signal of each 
transmitter on the signal bus is digitally polled.  The primary 
communication device sequentially polls each transmitter 
output on the bus.  Each transmitter has its own unique 
address that is assigned during configuration.  The address 
(1..15) allows the primary communication device to distinguish 
between transmitters on the bus.

Each transmitter on the bus is wired from the primary 
communication device to the positive (+) and negative (–) 
POWER (SIGNAL) terminals of the AWT210.  Connect all 
transmitters on the bus in parallel.

The minimum power supply voltage required for the loop is 
typically determined by:

•  minimum voltage supply = 14 V + (0.004 A x R)
•  minimum current supply = 0.004 A x T

Where:

•  R is the Load Resistance in ohms, and
•  T is the number of transmitters on the bus

       

   IMPORTANT (NOTE)   

 

 The equation for minimum supply voltage is based on 
a maximum output current of 4 mA.  In some cases 
other transmitters may use a multi-drop minimum 
current of greater than 4 mA.  Consult the vendor 
product instruction for multi-drop current values for 
other equipment on the bus..

The load resistance must include the system input resistance 
and the resistance of the wire.  Analog meters or measurement 
devices should not be connected to the bus since the 
transmitters on the bus are not delivering an analog process 
variable.

A secondary communication device can be connected anywhere 
there is access to the signal wires, as long as it is not connected 
directly across the power supply.

       

   IMPORTANT (NOTE)   

 

 Only one secondary device can communicate on the 
loop at any given time.

Sensor wiring and grounding

Refer to the AWT210 Operating Instructions (OI/AWT210-EN) 
for sensor wiring and grounding instructions.

Summary of Contents for AWT210

Page 1: ...al information on installation operation and maintenance For more information Further publications for the AWT210 transmitter are available for free download from www abb com measurement or by scannin...

Page 2: ...Transmitter functionality and operator interface controls 6 Process interface 6 Sensor Input Channels 6 Host interface 6 Analog output 6 Local interfaces jumpers and switches 6 Local controls and dis...

Page 3: ...RNING BODILY INJURY Installation operation maintenance and servicing must be performed by suitably trained personnel only in accordance with the information provided in this manual in accordance with...

Page 4: ...or disposal at no charge to the user ABB is committed to ensuring that the risk of any environmental damage or pollution caused by any of its products is minimized as far as possible IMPORTANT NOTE Fo...

Page 5: ...re sensor ORP Oxidation reduction potential DDL Device description language HART Highway addressable remote transducer HHT Hand held terminal Reference documents Document ID Title DS AWT210 EN AWT210...

Page 6: ...tory settings If powered up with SW1 in the OFF position the device retains previously saved user settings SW2 Write Protection If SW2 is in the ON position HW write protect shows as enabled and the u...

Page 7: ...022 amps x R ohms Load resistance must include any meters external to the AWT210 transmitter the wiring and the system input IMPORTANT NOTE The equation for minimum supply voltage is based on a maximu...

Page 8: ...tters on the bus Each transmitter on the bus is wired from the primary communication device to the positive and negative POWER SIGNAL terminals of the AWT210 Connect all transmitters on the bus in par...

Page 9: ...by enabling PDM compatibility at the following menu Device Setup PDM Compatibility Enable Device specific HART commands general Command Description 122 Login to Service Level 123 Read Board Object 124...

Page 10: ...Parameters 164 Read Factory Calibration Slope and Offset 252 Read PV Sensor Config Table 4 Device specific HART commands Two Electrode conductivity TE Device specific HART commands Toroidal Conductiv...

Page 11: ...figuration 220 Read Temperature Sensor and Compensation Configuration 221 Write pH Solution Coefficient Value 222 Write millivolt Solution Coefficient Value 223 Read Primary Variable Transfer Function...

Page 12: ...to make technical changes or modify the contents of this document without prior notice With regard to purchase orders the agreed particulars shall prevail ABB AG does not accept any responsibility wh...

Reviews: