ABB AWT210 Manual Download Page 7

AW T 210

  H A R T  2- W I R E  T R A N SM I T T ER  |  CO M/AW T 2 10/H A R T- EN  R E V.  B

7

HART point-to-point analog signal and power wiring (loop current mode enabled)

Make connections to the HART communication module as 
shown in Figure 2.

Do not connect secondary communication device directly 
across the power supply.

Figure 2  Analog mode wiring diagram

The signal wiring supplies all power to the transmitter. 

The power supply limits are 14.0 to 42.0 V DC  
(14 to 30 V DC for agency certified installation). 

The minimum supply voltage is determined by the loop 
resistance (R) as follows:

•  minimum supply = 14.0 (volt) + 0.022 (amps) x R (ohms)

Load resistance must include any meters external to the 
AWT210 transmitter, the wiring and the system input.

       

   IMPORTANT (NOTE)   

 

 The equation for minimum supply voltage is based on 
a maximum output current of 20 mA.  In some cases 
such as fail high or process variable over range 
condition, the output current limits to 21.5 mA. To 
support these cases, use 0.0215 instead of 0.020.

A secondary communication device can be connected anywhere 
there is access to the signal wires as long as it is not connected 
directly across the power supply.

      

   IMPORTANT (NOTE)

 

Only one secondary device can communicate on the 
loop at any given time.

+

+

+

+–

 

 

System power 

supply

High impedance 

controller, 

recorder  

or control 

system

HART compatible 

hand-held terminal 

(secondary  

communication device)

250 

W

Summary of Contents for AWT210

Page 1: ...al information on installation operation and maintenance For more information Further publications for the AWT210 transmitter are available for free download from www abb com measurement or by scannin...

Page 2: ...Transmitter functionality and operator interface controls 6 Process interface 6 Sensor Input Channels 6 Host interface 6 Analog output 6 Local interfaces jumpers and switches 6 Local controls and dis...

Page 3: ...RNING BODILY INJURY Installation operation maintenance and servicing must be performed by suitably trained personnel only in accordance with the information provided in this manual in accordance with...

Page 4: ...or disposal at no charge to the user ABB is committed to ensuring that the risk of any environmental damage or pollution caused by any of its products is minimized as far as possible IMPORTANT NOTE Fo...

Page 5: ...re sensor ORP Oxidation reduction potential DDL Device description language HART Highway addressable remote transducer HHT Hand held terminal Reference documents Document ID Title DS AWT210 EN AWT210...

Page 6: ...tory settings If powered up with SW1 in the OFF position the device retains previously saved user settings SW2 Write Protection If SW2 is in the ON position HW write protect shows as enabled and the u...

Page 7: ...022 amps x R ohms Load resistance must include any meters external to the AWT210 transmitter the wiring and the system input IMPORTANT NOTE The equation for minimum supply voltage is based on a maximu...

Page 8: ...tters on the bus Each transmitter on the bus is wired from the primary communication device to the positive and negative POWER SIGNAL terminals of the AWT210 Connect all transmitters on the bus in par...

Page 9: ...by enabling PDM compatibility at the following menu Device Setup PDM Compatibility Enable Device specific HART commands general Command Description 122 Login to Service Level 123 Read Board Object 124...

Page 10: ...Parameters 164 Read Factory Calibration Slope and Offset 252 Read PV Sensor Config Table 4 Device specific HART commands Two Electrode conductivity TE Device specific HART commands Toroidal Conductiv...

Page 11: ...figuration 220 Read Temperature Sensor and Compensation Configuration 221 Write pH Solution Coefficient Value 222 Write millivolt Solution Coefficient Value 223 Read Primary Variable Transfer Function...

Page 12: ...to make technical changes or modify the contents of this document without prior notice With regard to purchase orders the agreed particulars shall prevail ABB AG does not accept any responsibility wh...

Reviews: