QUICK START
CALIBRATION
B
-
9
Table B-2. Calibration Procedures
AV3
Calibration
Adjustment
Procedure
AV4
Calibration
Adjustment
Procedure
Zero
1. Turn on supply air. Apply a 4 mA
input signal to the positioner. The
actuator should be in the closed posi-
tion.
Zero
1. Turn on supply air. Pulse the posi-
tioner in order to arrive at the mini-
mum (closed) position.
2. Loosen the zero adjustment set-
screw (Fig.
) using a
-inch
Allen wrench.
2. Loosen the zero adjustment set-
screw (Fig.
) using a
-inch
Allen wrench.
3. Turn the zero adjustment nut
(clockwise to increase) until the 0
radial line on the cam intersects with
the center of the cam roller (Fig.
).
3. Turn the zero adjustment nut
(clockwise to increase) until the radial
line on the cam intersects with the
center of the cam roller (Fig.
4. Tighten the zero adjustment set-
screw.
4. Tighten the zero adjustment set-
screw.
Span
1. Apply 20 mA to the positioner. The
actuator should be in its full open
position.
Span
1. Pulse the Raise (TB1-4) terminal
until the actuator is in the full open
position.
2. Loosen the span adjustment screw
(Fig.
) using a
-inch Allen
wrench.
2. Loosen the span adjustment screw
(Fig.
) using a
-inch Allen
wrench.
3. Slide the span adjustment assem-
bly in the (Fig.
) appropriate direc-
tion (toward cam to increase) in order
to align the 100% radial line with the
center of the cam roller.
3. Slide the span adjustment assem-
bly in the (Fig.
) appropriate direc-
tion (toward cam to increase) in order
to align the 100% radial line with the
center of the cam roller.
4. Tighten the span adjustment
screw.
4. Tighten the span adjustment
screw. Refer to Table
for motor
speed adjustment information.
3 32
⁄
3 32
⁄
3 32
⁄
3 32
⁄
Table B-3. Motor Speed Adjustment (AV4 Only)
AV4 Calibration
Adjustment
Procedure
Motor Speed 1. Set the coarse adjustment potentiometer, located on the
EMI/electronics housing, to position 1.
2. Set the fine adjustment to the fastest speed (fully clock-
wise) (Fig.
3. Apply pulse inputs until the actuator reaches 0%.
4. Using a stopwatch measure the time it takes the actuator
to reach 100% by applying a constant increase signal.
5. Having obtained an actuator speed value in Step 4, use
Table
to determine the coarse speed adjustment setting
which encompasses the actuator speed.
6. AV4 calibration is complete.