POSITION TRANSMITTERS
CALIBRATION
A - 6
d. Tighten the set screw on the small gear hub.
NOTE:
If the mesh between the large and small gears is not tight,
adjust the position of the potentiometer mounting bracket (Fig.
so that backlash is eliminated.
e. Remove the ohmmeter from TB1-1 and TB1-2. Install the
cam, screw, flag, nut, and washer (Fig.
).
3. Connect the field wiring to the terminal block. Connect a DC volt-
meter between TB1-1 (-) and TB1-2 (+).
4. Move the actuator to the 80% position. Adjust the resistor in
series with the 24 VDC supply until the voltmeter reads 5 VDC.
5. Move the actuator to the 0% position to verify that the voltmeter
reads less than 5 VDC.
6. Move the actuator to the 100% position to verify that the voltme-
ter reads greater than 5 VDC.
7. Potentiometric calibration complete.
Calibrating the Four to 20 mA Position Transmitter
Labels located inside the positioner cover show the location of jump-
ers, test points, calibration pots, and field connection terminals for the
position transmitter (Fig.
and
).
1. Remove the FOR/REV jumpers, and place the CAL/OPER jump-
ers in the calibrate (CAL) position (Fig.
2. Move the actuator to the 50% output position.
Figure A-4. Location of Calibration Features
for 4 to 20 mA Position Transmitter
F O R W A R D
C AL IB R AT E
Z ER O
SPA N
O P E R ATE
T P 2(+)
T P 1(–)
R E V ER S E
T 00 7 8 9 A