Installation and operating instructions, ATS022
1SDH000760R0002, L4106
24
6.2.1 Control circuit of the automatic transfer switch ATS022
Figure 6.2
Control circuit diagram ATS022
6. Connecting
Digital
input
Description
DI1
Protection device on normal line status input
(0 open, 1 close)
DI2
Protection device on emergency line status
input (0 open, 1 close)
DI3
Logic enable/disable
DI4
Normal line protection device tripped input
(normally closed)
DI5
Emergency line protection device tripped input
(normally closed)
DI6
Normal line protection inserted (normally closed)
DI7
Emergency line protection inserted
(normally closed)
DI8
Generator alarm input
DI9
Command to force commutation
DI10
Command to startup generator
DI11
3rd circuit breaker status (bus tie) (0 open,
1 close)
Digital
output
Description
DO1
Output to open the protection device of the
normal line (normal open)
DO2
Output to close the protection device of the
normal line (normal open)
DO3
Output to open the protection device of the
emergency line (normal open)
DO4
Output to close the protection device of the
emergency line (normal open)
DO5
Output to control the start/stop of the
generator (exchange)
DO6
Signaling emergency / alarm (normal open)
DO9
Signaling protection device alarm (normal
open)
DO10
Signaling ATS manual mode (normal open)
DO11
Command disconnection protection devices
(exchange)
Table 6.1
Digital inputs / outputs, ATS022
KA00469
LINE 1
LINE 2
ATS022
not used
not used
Measur
ement
Measur
ement
Power
Logic enable/
disable
Modbus
not used
Command disconnections
protection devices
Summary of Contents for ATS022