The use of current transformer for other purpose 
then described above is forbidden if not agreed 
with the producer.

Routine test report
The routine test report of a current instrument 
transformer includes:

a)  verification of terminal markings;  
b)  inter-turn overvoltage test; 
c)  determination of errors.

There are two rating plates available for the trans-
former (one glued on the transformer body, the 
other in the by-pack kit).

On customer request the following information 
can be provided free of charge: 

•  theoretical current/voltage error and phase dis-

placement values;

•  theoretical excitation (magnetization) curves. 

Additional reports for supplementary charge, 
made available on request:

•  test report on accuracy;
•  excitation (magnetization) curves;
•  additional nameplates (if more than 2 are re-

quired);

•  verification tests for measuring cores (classes 

0.2;  0.2 S;  0.5;  0.5 S). 

5. Maintenance instructions

Excessive dust sediments or any other type of 
contamination is to be removed from the trans-
former using a soft brush, in a way not to damage 
the insulation or cables taken out from the trans-
former.

6. Transport & Storage

Permitted temperature for transport and storage 
ranges from -40°C to +105°C. During transport 
and storage the transformers have to be pro-
tected from direct impact of solar radiation. The 
transformers are delivered in wooden crates or 
fixed on transport pallets.

Transported transformers must be protected to 
avoid any damages. Right option of transport 
must be wisely chosen.

7. Disposal

Materials used in instrument transformers are 
considered as materials without environmental 
impact and materials are not toxic. Instrument 
transformers have to be disposed of in accor-
dance with national legislation relevant to do-
mestic waste disposal. 

8. Handling

All the manipulation has to be performed with 
great effort to prevent any damage risks. During 
manipulation with the hanging strips make sure 
that it was used equipment for minimalizing of 
forces applied to active parts (transformer coils) - 
cushioned hanging strips, tying direction accord-
ing picture. If necessary place between the strips 
and coil/flanges, suitable foam distances to pre-
vent of dangerous pressure to coil. Always check 
whether the last insulation layer of the coils is un-
damaged after manipulation. For flanges as well.

9. Normative references

IEC 61869-2  Current instrument transformers

ISO 12100       Machine safety – basic concepts, 

general  
principles of design

EN 50110-1   Operation of electrical installations

Current instrument transformers are designed, 
tested and manufactured in accordance with in-


04


04 Manipulation with 
the hanging strips

Summary of Contents for AT35

Page 1: ... PRODUCTS FOR HIGH VOLTAGE APPLICATION AT Current Instrument Transformer Instruction for Installation use and maintenance ...

Page 2: ...ructions 4 Mounting 4 Connection of transformer primary side 4 Connection of transformer secondary side 4 4 Instructions for use 5 Routine test report 5 5 Maintenance instructions before installation 5 6 Transport Storage 5 7 Disposal 5 8 Handling 5 9 Normative references 6 10 Dimensions 5 11 Lifetime 5 12 Service 7 Appendix 1 Examples of outlets 8 Appendix 2 Dimensional drawings AT35 and AT41 Dim...

Page 3: ...ended current 9 rated output burden 10 accuracy classes 11 year of manufacture 12 serial number Label abbreviation definitions 3 Instruction for installation General information Instrument transformer is an electrical equip ment and the electrical installation of the instru ment transformer can be done by skilled person nel only The level of experience age and eligibility criteria for persons work...

Page 4: ...hreaded rots are delivered on cus tomer request Connection of transformer primary side The AT transformers don t have its own primary conductor The primary conductor is designed as a bushing with its own insulation or insulated ca ble Connection of the transformer secondary side Secondary outlets are marked by color Which color is assigned to which wire you can see in ta ble below Outlets marking ...

Page 5: ...rage the transformers have to be pro tected from direct impact of solar radiation The transformers are delivered in wooden crates or fixed on transport pallets Transported transformers must be protected to avoid any damages Right option of transport must be wisely chosen 7 Disposal Materials used in instrument transformers are considered as materials without environmental impact and materials are ...

Page 6: ...ed IEC 60044 1 IEC 60044 6 IEC 61869 2 AS 60044 1 ČSN EN 60044 1 ČSN EN 60044 6 IEEE Std C57 13 6 2005 ANSI C57 13 1978 CSA Std CAN3 C13 M83 BS EN 60044 1 When agreed transformers made in accordance with other standards can also be supplied or in accordance with other release version of the above standards 10 Dimensions Dimensions of the current transformers acc ap pendix 2 11 Lifetime The product...

Page 7: ...7 Appendix 1 Examples of outlets ...

Page 8: ...d depends on customer request The fixing parts are a part of a delivery mounting parts can be ordered separately as an attachment Testing primary Secondary outlets SIGN VALUE Variant C NOTE Variant C with optional testing primary see catalogue and optional length of secondary outlets depending on customer request The fixing part are a part of delivery mounting parts can be ordered separately as an...

Page 9: ...ry secondary outlets screening electrodes is optional and depends on customer request The fixing parts are a part of a delivery mounting parts can be ordered separately as an attachment AT38 Testing primary Secondary outlets Secondary electrodes 1000 1 0 0 0 ...

Page 10: ...le lack of information in this document We reserve all rights in this document and in the subject matter and illustrations con tained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB Copyright 2018 ABB All rights reserved C O N TA C T U S ABB s r o EPDS Brno Videnska 117 619 00 Brno Czech Repu...