AquaMaster 3
Electromagnetic flowmeter
4 Start-Up and Operation
User Guide OI/FET2XX–EN Rev. E
31
4 Start-Up and Operation
4.1 Start-up
To start the AquaMaster 3 for the first time:
1.
Connect the external power source; mains / battery or renewable power source – see Section 3.5,
page 28.
2.
Remove transportation label.
3.
Cover the display area for a few seconds.
4.
Uncover the display area. The display is activated, the AquaMaster 3 performs a self-test and begins
communication with the sensor.
A successful connection is indicated by the message 'Pass' in the display window and normal
flowmeter operation commences.
Warning.
The battery pack used by AquaMaster 3 may present a risk of fire or chemical burns if mistreated.
Do not recharge, disassemble, heat above 100 °C (212 °F) or incinerate.
Replace battery pack with an ABB-supplied part only. Use of another battery may present a risk of
fire or explosion.
Dispose of all battery packs promptly. Keep away from children.
Dispose of battery packs in accordance with local regulations.
Where possible, recycle used batteries.
Contact the local environmental authority for further information regarding disposal or recycling
schemes for used batteries.
Operation at elevated temperatures (>45 °C [113 °F]) significantly shortens the battery capacity
and life.
Notes.
If the display shows 'Err 1', check the sensor wiring. If the fault is rectified, the transmitter restarts
automatically.
If the display shows 'Err 2 or 3', contact ABB.