ABB AF190-30 Operating Instructions Download Page 4

1SFC100008M0201     Nov 2018

4/4

ABB AB, Control Products

 

SE -721 61 Västerås, Sweden

Tel46 21 32 07 00

T46 21 12 60 01

http://www.abb.com/lowvoltage

2,9 Nm - 26 lb.in

165

M5

35

187

M5

43,8

AF(S)190, AF(S)205

 

AF(S)265, AF(S)305, AF(S)370

 

 

General

a very wide voltage range. 

Code-11…-14

Operation is done, as with conventional contactors, by applying and removing supply voltage on A1 

and A2. Closing 85% and opening at 55% of the lower  nominal voltage limit, which is indicated in the 

functional diagram.

A1/A2

1

X5

2
3

A1 A2

ON

OFF_N

COM

96

0V

95

+24 V

When used with switches the wiring can be done

according to diagram above.

Contactor

Start

Stop

Supply voltage

Relay

Note: Emergency stop should disconnect A1 and A2

Position

Contactor 

closed

Contactor 

open

Supply

Functional diagram

 

vo

(A1/A2)

ltage

Low

High

Normal range

Operationalrange

85% of lower voltage range level

55% of lower voltage range level

1

0

1
0

High

Low

Closed

Open

ON

OFF_N

Voltage

Position

5

1

2

3

ON OFF_N COM

Code-33 and -34 built-in PLC interface

Operation is controlled by separate logic control signals from for instance a PLC. Use of logic control 

requires a steady supply voltage on A1 and A2 within the rated voltage range, as described for 

code-11…-14. The function of the logic control signal will no longer be guaranteed when the supply 

voltage on A1 and A2 is removed. 

The logic control signals are operated with 24V d.c. There are two control signals (ON and OFF_N) and a 

common reference (COM). For the control signals, the function is guaranteed from 15V d.c. (6mA) to 33V 

d.c. (20mA).

The contactor is closed by a control signal ON and opened by removal of control signal from OFF_N. The 

functions are described in diagram below. “1” means 24V d.c. between the control signal and COM. “0” 

means no voltage between the control signal and COM. Minimum control signal pulse length for 

opening and closing is 10ms. To connect the PLC interface use cable dimension of max 1.5mm2.

Summary of Contents for AF190-30

Page 1: ...men werden Unsach gemäße Steuerspannungs oder Hochspannungsprüfungen über die Klemmen können zu Schäden an der elektronischen Steuerschaltung des Schützes führen Advertencia realizar test de alto voltaje en los terminales de bobina A1 y A2 Una tensión de control errónea o una alta tensión de test en los terminales puede dañar los circuitos electrónicos de control del contactor Avertissement que la...

Page 2: ...S 305 AF S 370 5 mm 13X 44X NC 21X 32X 22X 31X 14X 43X NO 31X 22X NO 43X 14X 44X 13X 32X 21X NC 1 2 CAL19 11 53X 84X NC 61X 72X 62X 71X 54X 83X NO 71X 62X NO 83X 54X 84X 53X 72X 61X NC 3 4 CAL19 11B 3 4 A1 A2 1L1 3L2 5L3 2T1 4T2 6T3 1 2 A1 A2 1L1 3L2 5L3 2T1 4T2 6T3 Pos 5 Pos 1 Pos 4 Pos 3 Pos 2 30 30 Pos 1 30 17X 28X 18X 27X NO NO 27X 18X 28X 17X 1 2 CEL19 10 1 2 A1 A2 1L1 3L2 5L3 2T1 4T2 6T3 NC ...

Page 3: ...я в средах категории А Применение в средах категории В может привести к возникновению нежелательных электромагнитных помех В этом случае могут потребоваться дополнительные меры защиты от помех According to UL 60947 4 1 Use wire Cu 75 C only AF S 190 AF S 205 Use Pressure Terminal Connectors ILSCO D 3608 ABB ref ATK185 or use Listed ZMVV 7 Wire Connectors and Soldering Lugs Wire connectors Cable po...

Page 4: ...el 55 of lower voltage range level 1 0 1 0 High Low Closed Open ON OFF_N Voltage Position 5 1 2 3 ON OFF_N COM Code 33 and 34 built in PLC interface Operation is controlled by separate logic control signals from for instance a PLC Use of logic control requires a steady supply voltage on A1 and A2 within the rated voltage range as described for code 11 14 The function of the logic control signal wi...

Reviews: