Section 5.5.12 Channel Adjustment on AO Board
3BSE 002 415R701 Rev A
5-79
Resetting
Stop the GETAB command as described in the preceding chapter.
Reset the values for CONV_PAR, FILTER_P and DEADB.
Connect the process input or the jumper in the same way as the reference resistor is connected.
5.5.12 Channel Adjustment on AO Board
All analog output boards are adjusted during manufacture for current output, which means that
units in which the voltage output is used may be readjusted to obtain the full accuracy. The same
applies to spares. The following channel setting can be of interest:
•
Adjustment of the zero point Z
•
Adjustment of gain G
•
Adjustment of the variable gain V
•
Setting of the limits L1, L2.
It is not certain that all circuit boards encountered in this connection have all of these adjustment
possibilities. Before the adjustment, jumper the circuit board for the mode (voltage, current) in
which it is to be used. The connection required is shown in
and
Execute the adjustments in the order in which they are described (Z, G, V, L1, L2).
The output signal is measured on the connection unit after the load is replaced with the
instrument in accordance with
and
Figure 5-22. Adjustment of Voltage Output
U
DVM
Z
G
L1
L2
Connection unit
Voltage output
Register
Data base AO ch
AC 450 SW
VALUE
Circuit board
and
D/A Conv.
Summary of Contents for Advant Controller 450
Page 1: ...Advant OCS with Master software GYDQW RQWUROOHU User s Guide 3BSE 002 415R701 Rev A ...
Page 26: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xvi ...
Page 30: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xx ...
Page 488: ... GYDQW RQWUROOHU 8VHU V XLGH SSHQGL DUGZDUH 0RGXOHV A 48 3BSE 002 415R701 Rev A ...
Page 508: ...Advant Controller 450 User s Guide Appendix D Item Designations D 12 3BSE 002 415R701 Rev A ...
Page 518: ...Advant Controller 450 User s Guide Appendix F Load Calculation F 4 3BSE 002 415R701 Rev A ...
Page 522: ...Advant Controller 450 User s Guide Appendix G Memory Calculation G 4 3BSE 002 415R701 Rev A ...
Page 528: ...Advant Controller 450 User s Guide Appendix H Halt Codes H 6 3BSE 002 415R701 Rev A ...
Page 562: ...Advant Controller 450 User s Guide Index iv 3BSE 002 415R701 Rev A ...
Page 563: ......
Page 564: ...3BSE 002 415R701 Rev A March 2000 ...