![ABB Advant Controller 450 User Manual Download Page 427](http://html.mh-extra.com/html/abb/advant-controller-450/advant-controller-450_user-manual_3016427.webp)
Advant
®
Controller 450 User’s Guide
Section 5.5.11 Adjustment of Analog Input and Output Boards
3BSE 002 415R701 Rev A
5-75
Adjustment Possibilities on Circuit Boards
shows the adjustments possible on the various analog input and output boards.
Key to the signs:
Z - Zero, G - Gain, B - Balance, S - Symmetry, V - Variable gain, L1/L2 - Limits
5.5.11.1 Channel Adjustment on DSAI 130
Channel adjustment consists of the following operations:
•
Zero-point adjustment Z
•
CMRR-balancing (Common Mode Rejection Ratio) B (= suppression of CMV).
Adjustment is normally not necessary except in exchange of components in this circuit.
•
Full scale adjustment G.
Table 5-3. Adjustment Possibilities on Analog Circuit Boards
Type
Channel adjustment
Common adjustment
Req. of DSFB 110
(1)
(1) If a potentiometer is not accessible from the front, place the board on an extension board DSFB 110.
DSAI 110
--
Z,G
--
DSAI 130
Z, B, G
Z, G, S
(2)
(2) Symmetry (S), which is adjusted in a test during manufacture, has the same effect as Gain (G),
but only on positive values.
Yes
DSAI 130A
The module is calibrated at production
DSAI 133
--
G, Automatic adjustment
(3)
(3) DSAI 133 and DSAX 110 have automatically adjusted zero and automatically adjusted Gain caused by an onboard adjustable
voltage reference.
Yes
DSAI 133A
The module is calibrated at production
DSAI 146
--
G
--
DSAI 155A
Automatic adjustment
Automatic adjustment
--
DSAX 110
--
G, Automatic adjustment
Yes
DSAO 110
Z, G, V, L1, L2
--
Yes
DSAO 120
Z, G
--
--
DSAO 120A
The module is calibrated at production
DSAO 130
G
--
Yes
DSAO 130A
The module is calibrated at production
DSAX 110A
The module is calibrated at production
DSTY 101
Z, G
--
--
Summary of Contents for Advant Controller 450
Page 1: ...Advant OCS with Master software GYDQW RQWUROOHU User s Guide 3BSE 002 415R701 Rev A ...
Page 26: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xvi ...
Page 30: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xx ...
Page 488: ... GYDQW RQWUROOHU 8VHU V XLGH SSHQGL DUGZDUH 0RGXOHV A 48 3BSE 002 415R701 Rev A ...
Page 508: ...Advant Controller 450 User s Guide Appendix D Item Designations D 12 3BSE 002 415R701 Rev A ...
Page 518: ...Advant Controller 450 User s Guide Appendix F Load Calculation F 4 3BSE 002 415R701 Rev A ...
Page 522: ...Advant Controller 450 User s Guide Appendix G Memory Calculation G 4 3BSE 002 415R701 Rev A ...
Page 528: ...Advant Controller 450 User s Guide Appendix H Halt Codes H 6 3BSE 002 415R701 Rev A ...
Page 562: ...Advant Controller 450 User s Guide Index iv 3BSE 002 415R701 Rev A ...
Page 563: ......
Page 564: ...3BSE 002 415R701 Rev A March 2000 ...