Advant Controller 450 Product Guide
Section 6.8 Trend Data Storage
3BSE 015 953R201 Rev B
6-9
See
for relative time error between events for different configurations. All events
connected to one Advant Controller 450.
6.8 Trend Data Storage
The Trend data storage capacity of Advant Controller 450 is shown in
.
NOTE
The CPU load and the RAM requirements must also be considered.
Table 6-7. Relative time errors between events (DI signals)
Bus
Events generated by
Relative time
error (ms)
Controller
Module/Calculated
Advant Fieldbus 100
AC 110/160
DI650
<2
AC 110/160
Calculated in AMPL
<2 + Sct
(1)
(1)
Sct means scan cycle time of reading I/O signals in the Advant Controller 55, 70, 110 or 160.
AC 70
Calculated in AMPL
<2 + Sct
RCOM/RCOM+
AC 110/160
DI650
<50
(2)
(2)
This value is valid for a fixed RCOM connection where there is a continuous clock synchronization over the
bus (at least once per minute). If dial-up phone lines are used the error is also dependent of the elapsed time
since the previous call (clock synchronization).
AC 110/160
Calculated in AMPL
<50 + Sct
AC 55
Calculated in AMPL
<50 + Sct
Table 6-8. Data logging capabilities
Aspect
Limit/Value
Max. No. of logs
15
Max. No. of variables / log
127
Max. No. of storable values
(1)
/ variable
(common to all variables in the log)
(1)Each value requires 5 byte of memory.
32767 (the free amount of RAM
usually sets a lower limit)
Log sampling intervals
(in discrete steps)
sec: 1, 2, 3,.. 30
min: 1, 2, 3, .. 30
h: 1, 2, 3, .. 24
week: 1
Summary of Contents for Advant Controller 450
Page 6: ...Advant Controller 450 Product Guide Table of Contents iv 3BSE 015 953R201 Rev B...
Page 8: ...Advant Controller 450 Product Guide Table of Contents vi 3BSE 015 953R201 Rev B...
Page 12: ...Advant Controller 450 Product Guide Table of Contents x 3BSE 015 953R201 Rev B...
Page 36: ...Advant Controller 450 Product Guide Chapter 3 Software Components 3 8 3BSE 015 953R201 Rev B...
Page 52: ...Advant Controller 450 Product Guide Chapter 4 Hardware Components 4 16 3BSE 015 953R201 Rev B...
Page 58: ...Advant Controller 450 Product Guide Chapter 5 Mechanical Design 5 6 3BSE 015 953R201 Rev B...
Page 119: ......
Page 120: ...3BSE 015 953R201 Rev B March 2001...