Parameter data
282
Fieldbus equivalent
Serial communication data between fieldbus adapter and drive is transferred in
integer format. Thus the drive actual and reference signal values must be scaled to
16/32-bit integer values. Fieldbus equivalent defines the scaling between the signal
value and the integer used in serial communication.
All the read and sent values are limited to 16/32 bits.
Example: If
is set from external control system,
an integer value of 10 corresponds to 1%.
Pointer parameter format in fieldbus communication
Value and bit pointer parameters are transferred between the fieldbus adapter and
drive as 32-bit integer values.
32-bit integer value pointers
When a value pointer parameter is connected to the value of another parameter, the
format is as follows:
For example, the value that should be written into parameter
to change its value to
0100 0000 0000 0000 0000 0001 0000 0111 = 1073742087 (32-bit integer).
When a value pointer parameter is connected to an application program, the format
is as follows:
Note:
Value pointer parameters which are connected to an application program
cannot be set via fieldbus (ie, read access only).
Bit
30…31
16…29
8…15
0…7
Name
Source type
Not in use
Group
Index
Value
1
-
1…255
1…255
Description
Value pointer is
connected to
parameter/signal.
-
Group of source
parameter
Index of source
parameter
Bit
30…31
24…29
0…23
Name
Source type
Not in use
Address
Value
2
-
0 … 2
24
-1
Description
Value pointer is
connected to application
program.
-
Relative address of
application program
variable
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...