![ABB ACSM1 Series Firmware Manual Download Page 93](http://html1.mh-extra.com/html/abb/acsm1-series/acsm1-series_firmware-manual_3347482093.webp)
Parameters and firmware blocks
93
Group
Local control and parameter access settings, restoration of default parameter
values, save of parameters into permanent memory.
16
16 SYSTEM
16.01
LOCAL LOCK
FW block: None
Selects the source for disabling local control (Take/Release button on the PC tool, LOC/REM key of
the panel). 1 = Local control disabled. 0 = Local control enabled.
WARNING!
Before activating, ensure that the control panel is not needed for stopping the
drive!
Bit pointer: Group, index and bit
16.02
PARAMETER LOCK
FW block: None
Selects the state of the parameter lock. The lock prevents parameter changing.
Note:
This parameter can only be adjusted after the correct pass code has been entered at parameter
PASS CODE.
(0)
LOCKED
Locked. Parameter values cannot be changed from the control panel.
(1)
OPEN
The lock is open. Parameter values can be changed.
(2)
NOT SAVED
The lock is open. Parameter values can be changed, but the changes
will not be stored at power switch off.
16.03
PASS CODE
FW block: None
After entering 358 at this parameter, parameter
The value reverts back to 0 automatically.
16.04
PARAM RESTORE
FW block: None
Restores the original settings of the application, i.e. parameter factory default values.
Note:
This parameter cannot be changed while the drive is running.
(0)
DONE
Restoration is completed.
(1)
RESTORE DEFS
All parameter values are restored to default values, except motor
data, ID run results, and fieldbus, drive-to-drive link and encoder
configuration data.
(2)
CLEAR ALL
All parameter values are restored to default values, including motor
data, ID run results and fieldbus and encoder configuration data. PC
tool communication is interrupted during the restoration. Drive CPU is
re-booted after the restoration is completed.
16.07
PARAM SAVE
FW block: None
Saves the valid parameter values to the permanent memory.
Note:
A new parameter value is saved automatically when changed from the PC tool or panel but not
when altered through a fieldbus connection.
Summary of Contents for ACSM1 Series
Page 1: ...ACSM1 Firmware Manual ACSM1 Speed and Torque Control Program...
Page 2: ......
Page 4: ......
Page 12: ...Table of contents 12...
Page 49: ...Drive control and features 49...
Page 282: ...Standard function blocks 282...
Page 306: ...Application program template 306...
Page 312: ...Control chain block diagrams 312...
Page 331: ...331...
Page 332: ...332...
Page 333: ......