572 Fieldbus control through a fieldbus adapter
Control word and Status word
The Control word is the principal means for controlling the drive from a fieldbus
system. It is sent by the fieldbus master station to the drive through the adapter
module. The drive switches between its states according to the bit-coded instructions
in the Control word, and returns status information to the master in the Status word.
For the ABB Drives communication profile, the contents of the Control word and the
Status word are detailed on pages
respectively. The drive states are
presented in the state diagram (page
).
When a transparent communication profile is selected eg. by parameter group
, the control word received from the PLC is available in
. The individual bits of the word can then be used for drive
control through bit pointer parameters. The source of the status word, for example
Debugging the network words
If parameter
, the Control word received from
the fieldbus is shown by parameter
, and the Status word
transmitted to the fieldbus network by
. This “raw” data is
very useful to determine if the fieldbus master is transmitting the correct data before
handing control to the fieldbus network.
References
References are 16-bit words containing a sign bit and a 15-bit integer. A negative
reference (indicating reversed direction of rotation) is formed by calculating the two’s
complement from the corresponding positive reference.
ABB drives can receive control information from multiple sources including analog
and digital inputs, the drive control panel and a fieldbus adapter module. In order to
have the drive controlled through the fieldbus, the module must be defined as the
source for control information such as reference. This is done using the source
selection parameters in groups
,
and
Debugging the network words
If parameter
, the references received from
the fieldbus are displayed by
.
Scaling of references
Note:
The scalings described below are for the ABB Drives communication profile.
Fieldbus-specific communication profiles may use different scalings. For more
information, see the manual of the fieldbus adapter.
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...