172 Parameters
Last speed
Drive generates a warning (
) and freezes
the speed (or frequency) to the level the drive was operating
at. The speed/frequency is determined on the basis of actual
speed using 850 ms low-pass filtering.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
3
Speed ref safe
Drive generates a warning (
) and sets the
speed to the speed defined by parameter
(or
is being used).
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
4
(Visible when
Specifies the analog input limits to be supervised. See
parameter
Note:
The number of active bits in this parameter depends on
the number of inputs on the extension module.
0000 0000b
0000 0000b …
0011 1111b
Activation of analog input supervision.
1 = 1
(Visible when
)
Selects a drive signal to be connected to digital input/output
DIO3 when parameter
is set to
For the available selections, see parameter
(Visible when
Triggers the analog input tuning function, which enables the
use of actual measurements as the minimum and maximum
input values instead of potentially inaccurate estimates.
Apply the minimum or maximum signal to the input and select
the appropriate tuning function.
See also the drawing at parameter
.
No action
Tuning action completed or no action has been requested.
The parameter automatically reverts to this value after any
tuning action.
0
AI1 min tune
The measured value of AI1 is set as the minimum value of AI1
into parameter
.
1
AI1 max tune
The measured value of AI1 is set as the maximum value of
AI1 into parameter
.
2
AI2 min tune
The measured value of AI2 is set as the minimum value of AI2
into parameter
.
3
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
AI1 < MIN
1 = Minimum limit supervision of AI1 active.
1
AI1 > MAX
1 = Maximum limit supervision of AI1 active.
2
AI2 < MIN
1 = Minimum limit supervision of AI2 active.
3
AI2 > MAX
1 = Maximum limit supervision of AI2 active.
4
AI3 < MIN
1 = Minimum limit supervision of AI3 active (FIO-11 only).
5
AI3 > MAX
1 = Maximum limit supervision of AI3 active (FIO-11 only).
6…15
Reserved
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...