Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
2
Eight data bits, even parity bit, one stop bit.
8 EVEN 1
3
Eight data bits, odd parity bit, one stop bit.
8 ODD 1
Enabled / uint16
Validates any changes in the EFB settings, or activates
silent mode.
Communication
control
58.6
0
Normal operation.
Enabled
1
Validates any changed EFB configuration settings.
Reverts automatically to
Refresh settings
2
Activates silent mode (no messages are transmitted).
Silent mode can be terminated by activating the
selection of this parameter.
Silent mode
- / uint16
Displays the status of the EFB communication.
This parameter is read-only.
Communication
diagnostics
58.7
1 = EFB initialization failed
Init failed
b0
1 = Node address not allowed by protocol
Addr config err
b1
1 = Drive not allowed to transmit
0 = Drive allowed to transmit
Silent mode
b2
Reserved
Autobauding
b3
1 = Errors detected (A/B wires possibly swapped)
Wiring error
b4
1 = Error detected: check parameters
and
Parity error
b5
1 = Error detected: check parameters
and
Baud rate error
b6
1 = 0 bytes received during last 5 seconds
No bus activity
b7
1 = 0 packets (addressed to any device) detected during
last 5 seconds
No packets
b8
1 = Errors detected (interference, or another device
with the same address on line)
Noise or addressing
error
b9
1 = 0 packets addressed to the drive received within
timeout (
Comm loss
b10
1 = No control word or references received within
timeout (
CW/Ref loss
b11
Reserved
Not active
b12
1 = Protocol-dependent status information
Protocol 1
b13
1 = Protocol-dependent status information
Protocol 2
b14
1 = Problem with calls to drive control program
Internal error
b15
1 = 1
0000h…FFFFh
0 / uint32
Displays a count of valid packets addressed to the
drive.
During normal operation, this number increases
constantly.
Can be reset from the control panel by keeping Reset
depressed for over 3 seconds.
Received packets
58.8
1 = 1 / 1 = 1
Number of received packets addressed to the drive.
0...4294967295
Parameters 481
Summary of Contents for ACS880 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Page 2: ......
Page 4: ......
Page 16: ...16 ...
Page 22: ...22 ...
Page 24: ...24 ...
Page 44: ...44 ...
Page 66: ...66 ...
Page 148: ...148 ...
Page 168: ...168 ...
Page 704: ...704 ...
Page 728: ...728 ...
Page 742: ...742 ...
Page 762: ...762 ...