Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
0.000 mA or V /
real32
Defines the minimum site value for analog input AI1.
Set the value actually sent to the drive when the analog
signal from plant is wound to its minimum setting.
See also parameter
.
AI1 min
12.17
1000 = 1 mA or V /
1000 = 1 mA or V
Minimum value of AI1.
-22.000 ... 22.000 mA
or V
20.000 mA or V /
real32
Defines the maximum site value for analog input AI1.
Set the value actually sent to the drive when the analog
signal from plant is wound to its maximum setting.
See also parameter
.
AI1 max
12.18
1000 = 1 mA or V /
1000 = 1 mA or V
Maximum value of AI1.
-22.000 ... 22.000 mA
or V
0.000 / real32
Defines the real internal value that corresponds to the
minimum analog input AI1 value defined by parameter
. (Changing the polarity settings of
and
can effectively invert the analog input.)
AI
scaled
(
12.12 )
AI
in
(
12.11 )
12.20
12.17
12.18
12.19
AI1 scaled at AI1 min
12.19
1 = 1 / 1000 = 1
Real value corresponding to minimum AI1 value.
-32768.000 ...
32767.000
1500.000; 1800.000
(95.20 b0) / real32
Defines the real internal value that corresponds to the
maximum analog input AI1 value defined by parameter
. See the drawing at parameter
AI1 scaled at AI1 max
12.20
1 = 1 / 1000 = 1
Real value corresponding to maximum AI1 value.
-32768.000 ...
32767.000
- / real32
Displays the value of analog input AI2 in mA or V
(depending on whether the input is set to current or
voltage by a hardware setting).
This parameter is read-only
AI2 actual value
12.21
1000 = 1 mA or V /
1000 = 1 mA or V
Value of analog input AI2.
-22.000 ... 22.000 mA
or V
Parameters 189
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...