60 Planning the electrical installation
Motor cable shield
If the motor cable shield is used as the sole protective earth conductor of the motor,
make sure that the conductivity of the shield is sufficient. See
on page
or see IEC 61439-1.
To effectively suppress radiated and conducted radio-frequency emissions, the cable
shield conductivity must be at least 1/10 of the phase conductor conductivity. To meet
the requirements, use a copper or an aluminum shield. The figure shows the
minimum requirements for the motor cable shield. It has a concentric layer of copper
wires with an open helix of copper tape or copper wire. The better and tighter the
shield, the lower the emission level and bearing currents.
Additional US requirements
Use type MC continuous corrugated aluminum armor cable with symmetrical grounds
or shielded power cable for the motor cables if metallic conduit is not used. For the
North American market, 600 V AC cable is accepted for up to 500 V AC. A 1,000 V
AC cable is required above 500 V AC (below 600 V AC). The power cables must be
rated for 75 °C (167 °F).
Conduit
Couple separate parts of a conduit together: bridge the joints with a ground conductor
bonded to the conduit on each side of the joint. Also bond the conduits to the drive
enclosure and motor frame. Use separate conduits for input power, motor, brake
resistor, and control wiring. When conduit is used, type MC continuous corrugated
aluminum armor cable or shielded cable is not required. A dedicated ground cable is
always required.
Note
: Do not run motor wiring from more than one drive in the same conduit.
1
Sheath
2
Copper wire shield
3
Helix of copper tape or copper wire
4
Filling
5
Cable conductors
1
3
4
5
2
Summary of Contents for ACS880-M04
Page 1: ...ABB machinery drives Hardware manual ACS880 M04 drive ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Safety instructions ...
Page 28: ...28 About the manual ...
Page 38: ...38 Operation principle and hardware description ...
Page 48: ...48 Planning the cabinet installation ...
Page 54: ...54 Mechanical installation ...
Page 72: ...72 Planning the electrical installation ...
Page 98: ...98 Electrical installation ...
Page 102: ...102 Start up ...
Page 108: ...108 Maintenance ...
Page 140: ...140 Technical data ...
Page 158: ...158 Mains chokes ...
Page 164: ...164 EMC filters 7 Attach the terminal blocks to the filter 1 6 5 4 3 ...
Page 166: ...166 EMC filters 6 Attach the terminal blocks to the filter 1 2 3 4 ...
Page 168: ...168 EMC filters ...
Page 182: ...Dimension drawings 182 Frame size R1 H1 H2 W D ...
Page 183: ...Dimension drawings 183 Frame size R2 H2 H1 W D ...
Page 184: ...Dimension drawings 184 Frame size R3 D W H1 H2 ...
Page 185: ...Dimension drawings 185 Frame size R4 W H1 H2 D ...
Page 187: ...187 Dimension drawings EMC filters type JFI x1 JFI A1 ...
Page 188: ...Dimension drawings 188 JFI B1 ...
Page 189: ...189 Dimension drawings EMC filters type JFI 0x ...
Page 191: ...191 Dimension drawings Brake resistors type JBR xx ...
Page 193: ...193 Dimension drawings ...
Page 195: ...www abb com drives www abb com drivespartners 3AXD50000028613 Rev A EN 2016 04 11 Contact us ...