56 Standard programposi features
Digital input/output DIO1 is used as a frequency input, DIO2 as a frequency output.
The number of digital inputs/outputs are increased using FIO-xx I/O extensions. See
(page
Settings
See parameter groups
•
•
Programmable relay outputs
The control unit has three relay outputs. The signal is indicated by the outputs are
selected using parameters.
Relay outputs are added using FIO-0x I/O extensions.
Settings
See parameter group
(page
).
Programmable I/O extensions
Inputs and outputs are added using FIO-xx I/O extension modules. One to three
modules are mounted on the slots of the control unit.
The table below shows the number of I/O on the control unit as well as optional
FIO-xx I/O extension modules.
Three I/O extension modules are activated and configured using parameter groups
14...16.
Note:
Each configuration parameter group contains parameters that display the
values of the inputs on that particular extension module. These parameters are the
only way of utilizing the inputs on I/O extension modules as signal sources. To
connect to an input, choose the setting
Other
in the source selector parameter, then
specify the appropriate value parameter (and bit, for digital signals) in group 14, 15
or 16.
Location
Digital
inputs
(DI)
Digital
I/Os
(DIO)
Analog
inputs
(AI)
Analog
outputs
(AO)
Relay
outputs
(RO)
Control unit
7
2
2
2
3
FIO-01
-
4
-
-
2
FIO-11
-
2
3
1
-
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...