Fault tracing 429
7183
BR excess temperature
Brake resistor temperature
has exceeded fault limit
defined by parameter
Stop drive. Let resistor cool down.
Check resistor overload protection
function settings (parameter group
).
Check fault limit setting, parameter
Check that braking cycle meets
allowed limits.
7184
Brake resistor wiring
Brake resistor short circuit or
brake chopper control fault.
Check brake chopper and brake
resistor connection.
Ensure brake resistor is not
damaged.
7191
BC short circuit
Short circuit in brake chopper
IGBT.
Ensure brake resistor is connected
and not damaged.
Check the electrical specifications
of the brake resistor against the
Hardware manual
.
Replace brake chopper (if
replaceable).
7192
BC IGBT excess
temperature
Brake chopper IGBT
temperature has exceeded
internal fault limit.
Let chopper cool down.
Check for excessive ambient
temperature.
Check for cooling fan failure.
Check for obstructions in the air
flow.
Check the dimensioning and
cooling of the cabinet.
Check resistor overload protection
function settings (parameter group
).
Check that braking cycle meets
allowed limits.
Check that drive supply AC voltage
is not excessive.
71B1
Motor fan
Programmable fault:
No feedback received from
external fan.
Check external fan (or other
equipment controlled) by the logic.
Check settings of parameters
…
7301
Motor speed feedback
Programmable fault:
No motor speed feedback
received.
Check the event log for an auxiliary
code. See appropriate actions for
each code at
(page
).
7310
Overspeed
Motor is turning faster than
highest allowed speed due to
incorrectly set
minimum/maximum speed,
insufficient braking torque or
changes in load when using
torque reference.
Check minimum/maximum speed
settings, parameters
and
Check adequacy of motor braking
torque.
Check need for brake chopper and
resistor(s).
Code
(hex)
Fault
Cause
What to do
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...