332 Parameters
Auto falling
One of the above modes is selected automatically
depending on the pulse frequency as follows:
5
(Visible when an absolute encoder is selected)
Enables the encoder zero pulse for the absolute encoder
input (X42) of the FEN-11 interface module.
Note: No zero pulse exists with serial interfaces, ie. when
parameter
,
,
Disable
Zero pulse disabled.
0
Enable
Zero pulse enabled.
1
(Visible when is resolver is selected)
Defines the number of pole pairs of the resolver.
1
1…32
Number of resolver pole pairs.
1 = 1
(Visible when TTL, TTL+ or HTL is selected)
Selects whether position estimation is used with encoder 1
to increase position data resolution or not.
Disable
Measured position used. (The resolution is 4 × pulses per
revolution for quadrature encoders, 2 × pulses per
revolution for single-track encoders.)
0
Enable
Estimated position used. (Uses position interpolation;
extrapolated at the time of data request.)
1
(Visible when an absolute encoder is selected)
Defines the number of bits used to indicate position within
one revolution. For example, a setting of 15 bits
corresponds to 32768 positions per revolution.
The value is used when parameter
. When parameter
is set to
parameter is internally set to 17.
0
0…32
Number of bits used in position indication within one
revolution.
1 = 1
(Visible when TTL, TTL+ or HTL is selected)
Selects whether calculated or estimated speed is used.
Estimation increases the speed ripple in steady state
operation, but improves the dynamics.
Disable
Last calculated speed used. (The calculation interval is
62.5 microseconds to 4 milliseconds.)
0
Enable
Estimated speed (estimated at the time of data request) is
used.
1
No.
Name/Value
Description
Def/
FbEq16
Pulse frequency of the
channel(s)
Used mode
< 2442 Hz
2442…4884 Hz
> 4884 Hz
Summary of Contents for ACS880 ESP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...