Draining the internal cooling circuit
You can drain the internal cooling circuit through the cooling unit as follows:
Note:
Draining coolant into the sewer system is not allowed.
WARNING!
High-pressure hot coolant may be present in the internal cooling circuit. No work
on the cooling circuit is allowed until the pressure is lowered down by stopping the
pumps and draining coolant.
1.
Lead the bleed hose into a bucket or other suitable container. Extend the standard
hoses when necessary.
2.
Open the bleed valve to let air displace the liquid.
3.
If required, dry the piping with compressed oil-free air of less than 6 bar (600 kPa).
4.
If the converter is to be stored in temperatures below 0 °C (32 °F),
•
dry the cooling circuit with air
•
fill the cooling circuit with a mixture of water and coolant according to section
protection and corrosion inhibition (page 122)
•
drain the cooling circuit again.
Cooling station control
See manufacturer’s instructions, the circuit diagrams delivered with the converter, and the
firmware manual.
120 Cooling and heating
Summary of Contents for ACS880-77CC
Page 1: ...ABB WIND TURBINE CONVERTERS ACS880 77CC wind turbine converters Hardware manual...
Page 2: ......
Page 4: ......
Page 10: ...10...
Page 17: ...5 1 3 4 6 8 7 2 Safety instructions 17...
Page 22: ...22...
Page 40: ...40...
Page 60: ...60...
Page 73: ...2a 3b 4c 5 Air flow direction is towards the converter module Maintenance 73...
Page 104: ...104...
Page 108: ...Description CAN bus connection XCAN XCAN 108 BCU x5 control unit...
Page 112: ...112 Dimension drawings...
Page 113: ...Dimension drawings 113...
Page 114: ...114 Dimension drawings...
Page 126: ...126...