Derating
Temperature derating
In the temperature range +40…50 °C (+104…122 °F), the rated output current is derated
by 1% for every added 1 °C (1.8 °F). The output current can be calculated by multiplying
the current given in the rating table by the derating factor (k):
T
1.00
0.90
+40 °C
+104 °F
+50 °C
+122 °F
k
0.80
Altitude derating
At altitudes from 1000 to 2000 m (3300 to 6561 ft) above sea level, the continuous output
currents given above must be derated 1% for every 100 m (328 ft). For a more accurate
derating, use the DriveSize PC tool.
Input and output voltages
Typical input and output voltages are listed below.
Output voltage U
2
(0…U
1
3-phase
symmetrical), ie, resistor (AC) connection
Input voltage U
1
(DC)
U
N
(V AC)
3 × 0…566 V DC
513…566 V DC.
400
This is indicated in the type designation label as
typical output voltage level 566 V DC.
This is indicated in the type designation label as
typical input voltage level 566 V DC.
3 × 0…707 V DC
513…707 V DC.
500
This is indicated in the type designation label as
typical output voltage levels 566 / 679 / 707 V
DC.
This is indicated in the type designation label as
typical input voltage levels 566 / 679 / 707 V DC.
3 × 0…976 V DC (UL, CSA: 848 V DC)
709…976 V DC (UL, CSA: 848 V DC).
690
This is indicated in the type designation label as
typical output voltage levels 742 / 849 / 976 (849
UL, CSA) V DC.
This is indicated in the type designation label as
typical input voltage levels 742 / 849 / 976 (849
UL, CSA) V DC.
Technical data 99
Summary of Contents for ACS880-604
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 604 3 phase brake units as modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 10: ...10 ...
Page 34: ...Overview of kits 34 Cabinet construction ...
Page 35: ...Stage 1 Installation of common parts Cabinet construction 35 10 ...
Page 36: ...Stage 2A Installation of DC busbars 1 without DC switch or charging 36 Cabinet construction ...
Page 37: ...Stage 2B Installation of DC busbars 1 with DC switch and charging Cabinet construction 37 10 ...
Page 39: ...Stage 4 Installation of incoming resistor busbars cable connection Cabinet construction 39 10 ...
Page 40: ...Stage 5 Installation of mounting plates and cable entries 40 Cabinet construction ...
Page 41: ...Stage 6 Installation of support plate Cabinet construction 41 10 ...
Page 42: ...Stage 7 Installation of shrouding 42 Cabinet construction ...
Page 43: ...Stage 8 Installation of brake chopper module Cabinet construction 43 10 ...
Page 44: ...44 ...
Page 48: ...48 ...
Page 56: ...56 ...
Page 74: ...74 ...
Page 76: ...76 ...
Page 112: ...Frame R8i 112 Dimension drawings ...
Page 113: ...Dimension drawings 113 ...
Page 114: ...Control electronics BCU control unit 114 Dimension drawings ...
Page 123: ...Miscellaneous components Quick connector for frame R8i Dimension drawings 123 ...
Page 124: ...124 Dimension drawings ...
Page 125: ... Insertion extraction ramp for frame R8i modules Dimension drawings 125 ...
Page 126: ...126 Dimension drawings ...
Page 127: ... CRBB 4 400 188 cooling fan 218 Dimension drawings 127 ...
Page 128: ...128 Dimension drawings ...