Default I/O diagram of the supply control unit
The diagram below shows the default I/O connections on the supply control unit (A51), and
describes the use of the connections in the supply unit. Under normal circumstances, the
factory-made wiring should not be changed.
The wire size accepted by all screw terminals (for both stranded and solid wire) is 0.5 …
2.5 mm
2
(24…12 AWG). The torque is 0.5 N·m (5 lbf·in).
XD2D
Drive-to-drive link
1
B
Drive-to-drive link (not in use by default)
2
A
3
BGND
4
Shield
D2D.TERM
Drive-to-drive link termination
1)
X485
RS485 connection
5
B
Not in use (not in use by default)
6
A
7
BGND
8
Shield
XRO1…XRO3
Relay outputs
11
NC
XRO1:
Charging
2)
(Energized = Closes charging contactor.)
250 V AC / 30 V DC / 2 A
12
COM
13
NO
21
NC
XRO2:
Fault(-1)
3)
(Energized = Indicates no fault.)
250 V AC / 30 V DC / 2 A
22
COM
23
NO
31
NC
XRO3:
MCB ctrl
2)
(Energized = Closes main contactor/breaker.)
250 V AC / 30 V DC / 2 A
32
COM
33
NO
XSTO
XSTO connector
1
OUT
XSTO connector. Both circuits (power module, control unit) must be closed for
the supply unit to start. (IN1 and IN2 must be connected to OUT.)
4)
2
SGND
3
IN1
4
IN2
5
IN1
Not in use
6
SGND
7
IN2
8
SGND
XDI
Digital inputs
1
DI1
Temp fault
3)
(0 = overtemperature)
2
DI2
Run / enable
3)
(1 = run / enable)
3
DI3
MCB fb
2)
(0 = main contactor/breaker open)
4
DI4
Not in use by default. Can be used for eg, auxiliary circuit breaker fault
5
DI5
Not in use by default. Can be used for eg, earth fault monitoring.
6
DI6
Reset
3)
(0 -> 1 = fault reset)
7
DIIL
Not in use by default. Can be used for eg, emergency stop.
XDIO
Digital input/outputs
1
DIO1
Not in use by default
2
DIO2
Not in use by default
3
DIOGND
Digital input/output ground
4
DIOGND
Digital input/output ground
XD24
Auxiliary voltage output
5
+24VD
+24 V DC 200 mA
5)
6
DICOM
Digital input ground
7
+24VD
+24 V DC 200 mA
5)
8
DIOGND
Digital input/output ground
DICOM=DIOGND
Ground selection switch
6)
XAI
Analog inputs, reference voltage output
1
+VREF
10 V DC,
R
L
1…10 kohm
2
-VREF
-10 V DC,
R
L
1…10 kohm
3
AGND
Ground
4
AI1+
Not in use by default.
0(2)…10 V,
R
in
> 200 kohm
7)
5
AI1-
6
AI2+
Not in use by default.
0(4)…20 mA,
R
in
= 100 ohm
8)
7
AI2-
XAO
Analog outputs
1
AO1
Zero
3)
0…20 mA,
R
L
< 500 ohm
2
AGND
3
AO2
Zero
3)
0…20 mA,
R
L
< 500 ohm
4
AGND
XPOW
External power input
1
+24VI
24 V DC, 2.05 A
2
GND
3
+24VI
4
GND
X12
Safety functions module connection
(not in use in supply units)
X13
Control panel connection
X205
Memory unit connection
Notes:
1)
Must be set to ON when the supply unit is the first or last unit on the drive-to-drive (D2D)
link. On intermediate units, set termination to OFF.
142 The control unit
Summary of Contents for ACS880-207
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 207 IGBT supply units Hardware manual ...
Page 2: ......
Page 4: ......
Page 53: ... 3 3 Electrical installation 53 11 ...
Page 54: ...3 54 Electrical installation ...
Page 81: ...4 5 6 7 8 6 10 10 Maintenance 81 ...
Page 94: ...5 6 10 3 4 7 9 8 94 Maintenance ...
Page 99: ... Maintenance 99 ...
Page 100: ... 100 Maintenance ...
Page 103: ...5 6 3 4 8 9 7 Maintenance 103 ...
Page 107: ...5 6 3 4 7 Maintenance 107 ...