86 Guidelines for planning the electrical installation
Implementing the functions provided by the FSO-xx
safety functions module (Q972 or +Q973)
The drive can be equipped with an FSO-xx safety functions module (Q972 or
+Q973) which enables the implementation of functions such as Safe brake control (SBC),
Safe stop 1 (SS1), Safe stop emergency (SSE), Safely limited speed (SLS) and Safe
maximum speed (SMS).
The settings of the FSO-xx are at default when delivered from the factory. The connectors
of the module are pre-wired to terminal block X68. The wiring of the external safety circuit
and configuration of the FSO-xx module are the responsibility of the machine builder.
The FSO-xx reserves the standard Safe torque off (STO) connection of the inverter control
unit. STO can still be utilized by other safety circuits through the FSO-xx.
For wiring instructions, safety data and more information on the functions provided by the
FSO-xx, refer to its manual.
Declaration of Conformity
Implementing the Power-loss ride-through function
Implement the power-loss ride-through function as follows:
Check that the power-loss ride-through function of the inverter unit is enabled with
parameter
30.31 Undervoltage control
in the ACS880 primary control program.
WARNING!
Make sure that the flying restart of the motor will not cause any
danger. If you are in doubt, do not implement the Power-loss ride-through
function.
The main contactor of the drive opens in a power-loss situation. When the power returns,
the contactor closes. However, if the power-loss situation lasts so long that the drive trips
on undervoltage, it must be reset and started again to continue operation. If the power-loss
situation lasts so long that the buffer module (see page
) runs out, the main contactor
remains open and the drive operates only after reset
and a new start.
With external uninterruptible control voltage (G307), the main contactor remains
closed in power-loss situations. If the power-loss situation lasts so long that the drive trips
on undervoltage, it must be reset and started again to continue operation.
Supplying power for the auxiliary circuits
The drive is equipped with an auxiliary control voltage transformer which supplies control
voltage, for example, for the control devices and cabinet fan(s).
The following options are to be supplied from external power sources:
•
+G300/+G301: Cabinet heaters and/or lighting (230 or 115 V AC; external fuse: 16 A)
•
+G307: Connection for an external uninterruptible power supply (230 or 115 V AC;
external fuse: 16 A) to the control unit and control devices when the drive is not
running
•
+G313: Power supply connection (230 V AC; external fuse 16 A) for a motor space
heater output.
Summary of Contents for ACS880-17
Page 1: ...ABB industrial drives Hardware manual ACS880 37 drives ...
Page 3: ......
Page 4: ......
Page 6: ......
Page 16: ...16 ...
Page 30: ...30 Introduction to the manual ...
Page 70: ...70 Mechanical installation ...
Page 105: ...Electrical installation 105 4 5 3 6 7 ...
Page 107: ...Electrical installation 107 5 6 4 3 ...
Page 108: ...108 Electrical installation 7 8 8 ...
Page 109: ...Electrical installation 109 9 10 ...
Page 111: ...Electrical installation 111 2 360 grounding detail a b b 1 5 a 11 b a PE 10 7 5 6 8 ...
Page 117: ...Electrical installation 117 PE 11 8 4 9 11 ...
Page 134: ...134 Control units of the drive ...
Page 140: ...140 Start up ...
Page 142: ...142 Fault tracing ...
Page 154: ...154 Maintenance 4 5 6 7 8 6 10 10 ...
Page 162: ...162 Maintenance 5 6 3 4 7 ...
Page 163: ...Maintenance 163 6 8 7 11 10 9 ...
Page 167: ...Maintenance 167 3 4b 4a 4b 8 ...
Page 185: ...Technical data 185 Declaration of Conformity ...
Page 186: ...186 Technical data ...
Page 196: ...196 Dimensions Dimension drawing examples Frame 1 R8i 1 R8i ...
Page 197: ...Dimensions 197 Frame 1 R8i 1 R8i top cable entry exit H351 H353 ...
Page 198: ...198 Dimensions Frame 1 R8i 1 R8i with brake choppers and resistors D150 D151 ...
Page 199: ...Dimensions 199 Frame 1 R8i 1 R8i with sine output filter E206 ...
Page 200: ...200 Dimensions Frame 2 R8i 2 R8i eg ACS880 37 1110A 3 IP22 ...
Page 201: ...Dimensions 201 Frame 2 R8i 2 R8i eg ACS880 37 1210A 3 IP54 ...
Page 204: ...204 Dimensions Frame 2 R8i 2 R8i with main breaker F255 and top entry top exit H351 H353 1 2 ...
Page 205: ...Dimensions 205 Frame 2 R8i 2 R8i with main breaker F255 and top entry top exit H351 H353 2 2 ...
Page 206: ...206 Dimensions Frame 3 R8i 3 R8i 1 2 ...
Page 207: ...Dimensions 207 Frame 3 R8i 3 R8i 2 2 ...
Page 208: ...208 Dimensions Frame 3 R8i 3 R8i with common motor terminal cubicle H359 1 2 ...
Page 209: ...Dimensions 209 Frame 3 R8i 3 R8i with common motor terminal cubicle H359 2 2 ...
Page 217: ...Dimensions 217 Sine filter E206 cubicle 1000 mm top cable exit ...
Page 221: ...Dimensions 221 Cubicle width 400 mm top cable exit Cubicle width 600 mm bottom cable exit ...
Page 222: ...222 Dimensions Cubicle width 600 mm top cable exit ...
Page 234: ...234 The Safe torque off function ...
Page 244: ...www abb com drives www abb com drivespartners 3AXD50000020437 Rev A EN 2015 02 06 Contact us ...