Connectors X50…X59
R8i modules contain a power supply (BDPS) that provides 24 V DC for the circuit boards
of the module. The 24 V DC voltage provided by the BDPS is also available on X53, and
can be used to power the BCU control unit of a single R8i module.
Note:
With parallel-connected R8i modules, it is strongly recommended to use an external 24 V DC
supply to power the BCU control unit.
The BDPS is powered internally from the DC link. An auxiliary voltage of 230 V AC or
115 V AC (selectable) can optionally be fed to terminal block X50 to power the BDPS even
when the DC link is not live. The selection between 115 V and 230 V is made with selector
plug X59. The setting can be changed by removing the two screws, turning the plug
180 degrees, and reinstalling the screws.
Note:
The Safe torque off (STO) safety function is only implemented in inverter units. Therefore,
the STO function can not be used in supply, brake and converter units. In supply, brake and
converter units, de-energizing any connection of STO IN (X52) connector stops the unit.
Note that this stop in supply or brake module is not safety related and must not be used for
safety function purposes.
The “24V” inputs on X52 must be connected to +24 V (on connector X53, for example) on
each module. On a new module, a jumper wire set installed at the factory makes this
connection.
Operation principle and hardware description 23
Summary of Contents for ACS880-1604LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 1604LC DC DC converter modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 12: ...12 ...
Page 16: ...16 ...
Page 34: ...34 ...
Page 42: ...Kits for ACS880 1604LC R8i unit in Rittal VX25 cabinets 42 Cabinet construction ...
Page 43: ...Stage 1 Installation of common parts Cabinet construction 43 10 ...
Page 45: ...Stage 3 Module installation parts Cabinet construction 45 10 ...
Page 46: ...Stage 4 DDC and energy storage connection 46 Cabinet construction ...
Page 47: ...Stage 5A DC connection with charging Cabinet construction 47 10 ...
Page 48: ...Stage 5B DC connection without charging 48 Cabinet construction ...
Page 49: ...Stage 6 Cooling components Cabinet construction 49 10 ...
Page 50: ...Stage 7 DDC module and filter installation 50 Cabinet construction ...
Page 51: ...Stage 8 Swing frame and shroud installation Cabinet construction 51 10 ...
Page 58: ...58 ...
Page 72: ...72 ...
Page 124: ...124 ...
Page 138: ...138 ...
Page 148: ...148 ...
Page 150: ...R8i DC DC converter module 150 Dimension drawings ...
Page 151: ...BDCL filter module Dimension drawings 151 ...
Page 152: ...Quick connector 152 Dimension drawings ...
Page 153: ...BCU control unit Dimension drawings 153 ...
Page 154: ...BAMU voltage current measurement unit Dimensions in mm 1 mm 0 0394 in 154 Dimension drawings ...