Derating
■
Ambient temperature derating
In the temperature range +45…55 °C (+113…131 °F), the rated output current is derated
by 0.5 percentage points for every added 1 °C (1.8 °F). The output current can be calculated
by multiplying the current given in the rating table by the derating factor
(k)
:
134 Technical data
Ratings
Definitions
Derating
Ambient temperature derating
In the temperature range +45…55 °C (+113…131 °F), the rated output current is derated
by 0.5 percentage points for every added 1 °C (1.8 °F). The output current can be
calculated by multiplying the current given in the rating table by the derating factor (
k
):
Module type
ACS880-304LC...
No overload use
Light overload
use
Heavy-duty
use
I
1
I
2
I
max
S
n
I
max
P
n
I
Ld
P
Ld
I
Hd
P
Hd
A (AC) A (DC) A (DC)
kVA
A (AC) kW (DC) A (DC)
kW
(DC)
A (DC)
kW
(DC)
U
N
= 690 V
-0820A-7+A019
820
1000
1400
980
1143
932
960
895
800
745
-1540A-7+A019
1540
1880
2632
1840
2149
1752
1805
1682
1504
1401
-2290A-7+A019
2290
2805
3927
2737
3206
2614
2693
2509
2244
2091
-3040A-7+A019
3040
3720
5208
3633
4252
3466
3571
3328
2976
2773
3AXD00000601909.XLS
Nominal ratings
U
N
Nominal input voltage. For
U
1
, see
Electrical power network specification
on page
139
. For
U
2
, see
DC connection data
on page
139
.
I
1
Continuous rms input (AC) current. No overload capability at the coolant temperature of 40 °C
(104 °F) and air temperature of 45 °C (113 °F).
I
2
Continuous rms output (DC) current. No overload capability at the coolant temperature of 40 °C
(104 °F) and air temperature of 45 °C (113 °F).
I
max
Maximum output (DC) current. Available for 10 s at start, otherwise as long as allowed by module
temperature.
S
n
Nominal apparent (AC) power
I
max
Maximum input (AC) current
P
n
Nominal output (DC) power
Light-overload use (50% overload capability) ratings
I
Ld
Continuous current. 50% overload is allowed for one minute every 5 minutes.
P
Ld
Output power in light-overload use
Heavy-duty use (50% overload capability) ratings
I
Hd
Continuous current. 50% overload is allowed for one minute every 5 minutes.
P
Hd
Output power in heavy-duty use
T
1.00
0.95
+45 °C
+113 °F
+55 °C
+131 °F
k
0.90
ACS880-304LC ACS880-104LC_ambient temp derating curve.pdf
■
Altitude derating
At altitudes from 1000 to 4000 m (3281 to 13123 ft) above sea level, the output current
derating is 1 percentage point for every added 100 m (328 ft). For example, the derating
factor for 1500 m (4921 ft) is 0.95.
For a more accurate derating, use the DriveSize PC tool.
Type equivalence table
BDCL filters
4)
Frame
Basic module type
DC/DC converter
module type
Cabinet-installed unit
type
Qty
Type
ACS880-104LC…
3)
ACS880-1604LC…
2)
ACS880-1607LC…
1)
U
N
= 690 V
1
BDCL-14LC-7
R8i
0480A-7
0400A-7
0400A-7
1
BDCL-14LC-7
R8i
0530A-7
0500A-7
0500A-7
1
BDCL-15LC-7
R8i
0600A-7
0600A-7
0600A-7
1
BDCL-15LC-7
R8i
0670A-7
0700A-7
0700A-7
1
BDCL-15LC-7
R8i
0750A-7
0800A-7
0800A-7
1
BDCL-15LC-7
R8i
0850A-7
0900A-7
0900A-7
2
BDCL-14LC-7
2×R8i
0530A-7
1000A-7
1000A-7
2
BDCL-15LC-7
2×R8i
0600A-7
1200A-7
1200A-7
2
BDCL-15LC-7
2×R8i
0670A-7
1400A-7
1400A-7
2
BDCL-15LC-7
2×R8i
0750A-7
1600A-7
1600A-7
2
BDCL-15LC-7
2×R8i
0850A-7
1800A-7
1800A-7
1)
Cabinet-installed units available from ABB
2)
DC/DC converter unit types available from ABB as modules
3)
R8i converter modules used. The quantity of the modules is shown in the frame column.
4)
BDCL filter type and quantity
Technical data 127
Summary of Contents for ACS880-1604LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 1604LC DC DC converter modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 12: ...12 ...
Page 16: ...16 ...
Page 34: ...34 ...
Page 42: ...Kits for ACS880 1604LC R8i unit in Rittal VX25 cabinets 42 Cabinet construction ...
Page 43: ...Stage 1 Installation of common parts Cabinet construction 43 10 ...
Page 45: ...Stage 3 Module installation parts Cabinet construction 45 10 ...
Page 46: ...Stage 4 DDC and energy storage connection 46 Cabinet construction ...
Page 47: ...Stage 5A DC connection with charging Cabinet construction 47 10 ...
Page 48: ...Stage 5B DC connection without charging 48 Cabinet construction ...
Page 49: ...Stage 6 Cooling components Cabinet construction 49 10 ...
Page 50: ...Stage 7 DDC module and filter installation 50 Cabinet construction ...
Page 51: ...Stage 8 Swing frame and shroud installation Cabinet construction 51 10 ...
Page 58: ...58 ...
Page 72: ...72 ...
Page 124: ...124 ...
Page 138: ...138 ...
Page 148: ...148 ...
Page 150: ...R8i DC DC converter module 150 Dimension drawings ...
Page 151: ...BDCL filter module Dimension drawings 151 ...
Page 152: ...Quick connector 152 Dimension drawings ...
Page 153: ...BCU control unit Dimension drawings 153 ...
Page 154: ...BAMU voltage current measurement unit Dimensions in mm 1 mm 0 0394 in 154 Dimension drawings ...