Use as motor cabling
Use as input power cabling
Cable type
Yes with motors up to 100 kW
(135 hp). A potential equaliza-
tion between the frames of mo-
tor and driven equipment is re-
quired.
Yes
Shielded (Al/Cu shield or ar-
mor)
1)
four-conductor cable
(three phase conductors and
a PE)
No
Yes
PE
WARNING!
If you use unshielded
single-core cables in an
IT network, make sure
that the non-conductive
outer sheath (jacket) of
the cables have good
contact with a properly
grounded conductive sur-
face. For example, install
the cables on a properly
grounded cable tray. Oth-
erwise voltage may be-
come present on the non-
conductive outer sheath
of the cables, and there
is even a risk of an elec-
tric shock.
A single-core cable system:
three phase conductors and
PE conductor on cable tray
L1
L3
L2
L2
L1
L3
L3
L2
L1
Preferable cable arrangement
to avoid voltage or current un-
balance between the phases
1) Armor may act as an EMC shield, as long as it provides the same performance as a concentric EMC shield
of a shielded cable. To be effective at high frequencies, the shield conductivity must be at least 1/10 of the
phase conductor conductivity. The effectiveness of the shield can be evaluated based on the shield inductance,
which must be low and only slightly dependent on frequency. The requirements are easily met with a copper
or aluminum shield/armor. The cross-section of a steel shield must be ample and the shield helix must have
a low gradient. A galvanized steel shield has a better high-frequency conductivity than a non-galvanized steel
shield.
Not allowed power cable types
Use as motor cabling
Use as input power cabling
Cable type
No
No
PE
Symmetrical shielded cable
with individual shields for each
phase conductor
66 Guidelines for planning the electrical installation
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...
Page 225: ... Declarations of conformity The Safe torque off function 225 ...