manner which produces a conductance equivalent to that which results from the
application of this table.
Minimum cross-sectional area of the corres-
ponding protective conductor
Sp (mm
2)
Cross-sectional area of the phase conduct-
ors
S (mm2)
S
1)
S ≤ 16
16
16 < S ≤ 35
S/2
35 < S
1) To comply with standard IEC/EN 61800-5-1:
•
use a protective earth conductor with a minimum cross-sectional area of 10 mm2 Cu or 16 mm2 Al (as an
alternative when aluminum cables are permitted),
or
•
use a second protective earth conductor of the same cross-sectional area as the original protective earth
conductor,
or
•
use a device that automatically disconnects the supply if the protective earth conductor is damaged.
If the protective earth conductor is separate (that is, it does not form part of the input power cable or the input
power cable enclosure), the minimum cross-sectional area must be:
•
2.5 mm2 when the conductor is mechanically protected,
or
•
4 mm2 when the conductor is not mechanically protected.
■
Typical power cable sizes
See the technical data.
■
Power cable types
Preferred power cable types
This section presents the preferred cable types. Make sure that the selected cable type
also complies with local/state/country electrical codes.
Use as motor cabling
Use as input power cabling
Cable type
Yes
Yes
PE
Symmetrical shielded (or ar-
mored) cable with three phase
conductors and concentric PE
conductor as shield (or armor)
64 Guidelines for planning the electrical installation
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...
Page 225: ... Declarations of conformity The Safe torque off function 225 ...