• Make sure that the drive type designation label includes the applicable marking.
•
DANGER - Risk of electric shock.
After disconnecting the input power, always
wait for 5 minutes to let the intermediate circuit capacitors discharge before you start
working on the drive, motor or motor cable.
• The drive is to be used in a heated, indoor controlled environment. The drive must
be installed in clean air according to the enclosure classification. Cooling air must
be clean, free from corrosive materials and electrically conductive dust.
• The cables located within the motor circuit must be rated for at least 75 °C in
UL-compliant installations.
• The input cable must be protected with fuses or circuit breakers. These protective
devices provide branch circuit protection in accordance with the national regulations
(National Electrical Code (NEC) or Canadian Electrical Code). Obey also any other
applicable local or provincial codes.
Suitable UL fuses are listed in section
and circuit breakers in
section
Circuit breakers (UL) (page 177)
WARNING!
The opening of the branch-circuit protective device may be an indication that
a fault current has been interrupted. To reduce the risk of fire or electric shock,
current-carrying parts and other components of the device should be examined
and replaced if damaged.
• The drive provides motor overload protection. This feature is not enabled when the
drive leaves the ABB factory. For enabling this motor overload protection, see the
firmware manual.
• The drive overvoltage category according to IEC 60664-1 is III
• To maintain the environment integrity of the enclosure, replace the cable grommets
with field-installed industrial conduit hubs or closure plates required by the enclosure
type (or better).
Declarations of conformity
See the chapter
The Safe torque off function (page 209)
Design lifetime expectancy
The design lifetime expectancy of the drive and its overall components exceeds ten (10)
years in normal operating environments. In some cases, the drive can last 20 years or
more. To achieve a long lifetime of the product the manufacturer’s instructions for sizing
the drive, installation, operational conditions and preventive maintenance schedule shall
be followed.
Technical data 199
Summary of Contents for ACS880-11
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 11 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 52: ...52 ...
Page 82: ...82 ...
Page 95: ...R6 R8 IP21 R6 R8 IP55 Electrical installation IEC 95 ...
Page 103: ...R6 1 5 N m 0 5 N m Electrical installation IEC 103 ...
Page 104: ...R8 1 5 N m 0 5 0 6 N m 104 Electrical installation IEC ...
Page 116: ...R6 R8 UL Type 1 R6 R8 UL Type 12 116 Electrical installation North America NEC ...
Page 142: ...142 ...
Page 154: ... Fan arrow must point up 154 Maintenance ...
Page 160: ...160 ...
Page 181: ... Package dimensions R6 R3 R8 Technical data 181 ...
Page 202: ...R3 IP21 UL Type 1 3AXD50000045323 202 Dimension drawings ...
Page 203: ...R3 Option B056 IP55 UL Type 12 3AXD50000045322 Dimension drawings 203 ...
Page 204: ...R6 IP21 UL Type 1 3AXD50000045353 204 Dimension drawings ...
Page 205: ...R6 Option B056 IP55 UL Type 12 3AXD50000045352 Dimension drawings 205 ...
Page 206: ...R8 IP21 UL Type 1 3AXD50000047667 206 Dimension drawings ...
Page 207: ...R8 Option B056 IP55 UL Type 12 3AXD50000047667 Dimension drawings 207 ...
Page 208: ...208 ...
Page 225: ... Declarations of conformity The Safe torque off function 225 ...