connect three out of five (or six out of ten, etc.) cables to the cubicle with three modules,
the remaining two out of five (four out of ten) cables to the cubicle with two modules.
■
Additional terminal block X504 (L504)
The standard terminal blocks of the drive control unit are wired to the additional terminal
block at the factory for customer control wiring. The terminals are spring loaded.
Cables accepted by the terminals:
•
solid wire 0.08 to 4 mm2
•
stranded wire with ferrule 0.14 to 2.5 mm2
•
stranded wire without ferrule 0.08 to 2.5 mm2 (28 to 12 AWG).
Stripping length: 10 mm.
Note:
The optional modules inserted in the slots of the control unit (or optional FEA-03 extension
adapter) are not wired to the additional terminal block. The customer must connect the
optional module control wires directly to the modules.
■
Starter for auxiliary motor fan (oM6xx)
What the option contains
The option provides switched and protected connections for 3-phase auxiliary motor fans.
Each fan connection is equipped with
•
fuses
•
a manual motor starter switch with an adjustable current limit
•
a contactor controlled by the drive, and
•
terminal block X601 for customer connections.
The number of connections must be specified when ordering. The maximum number of
connections available depends on the current requirement. The lower current ratings allow
up to four fan connections (eg. 4M602), while the highest current rating only allows
one (eg. +M610). For more information, refer to
ACS-880-X7 single drives ordering
information
(3AXD10000052815, available on request).
Description
The output for the auxiliary fan is wired from the 3-phase supply voltage to terminal block
X601 through a motor starter switch and a contactor. The contactor is operated by the drive.
The 230 V AC control circuit is wired through a jumper on the terminal block; the jumper
can be replaced by an external control circuit.
The starter switch has an adjustable trip current limit, and can be opened to permanently
switch the fan off.
The statuses of both the starter switch and the fan contactor are wired to the terminal block.
See the circuit diagrams delivered with the drive for the actual wiring.
44 Operation principle and hardware description
Summary of Contents for ACS880-07CLC
Page 1: ...ABB industrial drives Hardware manual ACS880 07CLC drives ...
Page 2: ......
Page 4: ......
Page 64: ...64 ...
Page 82: ...82 ...
Page 91: ...PE PE 10 13 12 22 Electrical installation 91 ...
Page 122: ...122 ...
Page 124: ...124 ...
Page 132: ...5 4 11 7 6 8 132 Maintenance ...
Page 133: ...14 15 16 12 13 17 Maintenance 133 ...
Page 141: ...5 Set the real time clock Maintenance 141 ...
Page 142: ...142 ...
Page 150: ...150 ...
Page 176: ...ACS880 07CLC 0390A 7 C121 marine construction 176 Dimensions ...
Page 177: ...ACS880 07CLC 1310A 7 Dimensions 177 ...
Page 178: ...ACS880 07CLC 2180A 7 C121 marine construction 178 Dimensions ...
Page 179: ...ACS880 07CLC 3260A 7 C121 marine construction Dimensions 179 ...
Page 181: ... 2 D8D Dimensions 181 ...
Page 182: ... 3 D8D 182 Dimensions ...
Page 183: ... 4 D8D Dimensions 183 ...
Page 185: ...Inverter module cubicle with two R8i modules bottom cable exit Dimensions 185 ...
Page 186: ...Inverter module cubicle with three R8i modules bottom cable exit 186 Dimensions ...
Page 187: ...Brake chopper cubicle D150 Dimensions 187 ...
Page 188: ...188 ...
Page 202: ...202 ...
Page 211: ......
Page 212: ......
Page 214: ...Contact us www abb com drives 3AXD50000131457 Rev A EN EFFECTIVE 2018 03 09 3AXD50000131457A ...