138 Technical data
sufficient. If in doubt, the supply transformer with static screening between the primary
and secondary windings can be used.
2. An EMC plan for preventing disturbances is drawn up for the installation. A template is
available from the local ABB representative.
3. The motor and control cables are selected as specified in the hardware manual.
4. The drive is installed according to the instructions given in the hardware manual.
WARNING!
A drive of category C4 is not intended to be used on a low-voltage public
network which supplies domestic premises. Radio frequency interference is expected if
the drive is used on such a network.
UL marking
cULus Listing is pending for the drive modules.
UL checklist
•
The drive module is to be used in a heated, indoor controlled environment. The drive
module must be installed in clean air according to enclosure classification. Cooling air
must be clean, free from corrosive materials and electrically conductive dust. See
page
•
The maximum ambient air temperature is 40 °C (104 °F) at rated current. The current
is derated for 40 to 50 °C (104 to 122 °F).
•
The drive module is suitable for use in a circuit capable of delivering not more than
100,000 rms symmetrical amperes, 600 V maximum when the input cable is protected
with class T fuses. The ampere rating is based on tests done according to UL 508C.
•
The cables located within the motor circuit must be rated for at least 75 °C (167 °F) in
UL-compliant installations.
•
The input cable must be protected with fuses. Circuit breakers must not be used
without fuses in the USA. For suitable circuit breakers, contact your local ABB
representative. Suitable IEC (class aR) fuses for drive protection are listed on page
and UL fuses on page
.
•
For installation in the United States, branch circuit protection must be provided in
accordance with the National Electrical Code (NEC) and any applicable local codes.
To fulfill this requirement, use the UL classified fuses.
Low voltage
Equipment
Low voltage
Equipment
Equipment
(victim)
Supply transformer
Medium voltage network
Static screen
Point of measurement
Drive
Neighboring network
Summary of Contents for ACS880-04F
Page 1: ...ABB industrial drives Hardware manual ACS880 04F drive modules ...
Page 4: ......
Page 24: ...24 Introduction to the manual ...
Page 46: ...46 Guidelines for planning the mechanical installation ...
Page 102: ...102 Installation checklist ...
Page 106: ...106 Fault tracing ...
Page 135: ...Technical data 135 Declaration of Conformity ...
Page 136: ...136 Technical data ...
Page 140: ...140 Technical data ...
Page 142: ...142 Dimension drawings Standard configuration IP20 UL Open Type ...
Page 143: ...Dimension drawings 143 Drive module with options E208 and H370 IP20 UL Open Type ...
Page 144: ...144 Dimension drawings Drive module with options 0B051 E208 0H371 IP00 UL Open Type ...
Page 145: ...Dimension drawings 145 Drive module with options 0B051 E208 0H371 C217 IP00 UL Open Type ...
Page 146: ...146 Dimension drawings Drive module with options 0B051 0H371 IP00 UL Open Type ...
Page 147: ...Dimension drawings 147 Mounting plate 3AXD50000038119 ...
Page 148: ...148 Dimension drawings 3AXD50000038119 ...
Page 149: ...Dimension drawings 149 External control unit 3axd50000011687 ...
Page 150: ...150 Dimension drawings ...
Page 164: ...164 Safe torque off function ...