Grounding requirements
This section gives general requirements for grounding the drive. When you plan the
grounding of the drive, obey all the applicable national and local regulations.
The conductivity of the protective earth conductor(s) must be sufficient.
Unless local wiring regulations state otherwise, the cross-sectional area of the
protective earth conductor must agree with the conditions that require automatic
disconnection of the supply required in 411.3.2 of IEC 60364-4-41:2005 and be capable
of withstanding the prospective fault current during the disconnection time of the
protective device. The cross-sectional area of the protective earth conductor must be
selected from the table below or calculated according to 543.1 of IEC 60364-5-54.
This table shows the minimum cross-sectional area of the protective earth conductor
related to the phase conductor size according to IEC/UL 61800-5-1 when the phase
conductor(s) and the protective earth conductor are made of the same metal. If this
is not so, the cross-sectional area of the protective earth conductor must be
determined in a manner which produces a conductance equivalent to that which results
from the application of this table.
Minimum cross-sectional area of the corresponding
protective earth conductor
S
p
(mm
2
)
Cross-sectional area of the phase conductors
S (mm
2
)
S
1)
S ≤ 16
16
16 < S ≤ 35
S/2
35 < S
1) For the minimum conductor size in IEC installations, refer to
Additional grounding requirements – IEC
.
If the protective earth conductor is not part of the input power cable or input power
cable enclosure, the minimum permitted cross-sectional area is:
•
2.5 mm
2
if the conductor is mechanically protected,
or
•
4 mm
2
if the conductor is not mechanically protected. If the equipment is
cord-connected, the protective earth conductor must be the last conductor to be
interrupted if there is a failure in the strain relief mechanism.
Guidelines for planning the electrical installation 69
Summary of Contents for ACS880-04F-504A-3
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 04F drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 36: ...36 ...
Page 44: ...44 ...
Page 50: ...50 Mechanical installation ...
Page 56: ...56 ...
Page 116: ...116 ...
Page 122: ...4 3 2 122 Maintenance ...
Page 128: ...128 ...
Page 143: ... Package dimensions Package dimensions without IP shroud kit Technical data 143 ...
Page 158: ...158 ...
Page 160: ...Standard configuration IP20 UL Type Open 160 Dimension drawings ...
Page 161: ...Drive module with options E208 and H370 IP20 UL Type Open Dimension drawings 161 ...
Page 162: ...Drive module with options 0B051 E208 0H371 IP00 UL Type Open 162 Dimension drawings ...
Page 163: ...Drive module with options 0B051 E208 0H371 C217 IP00 UL Type Open Dimension drawings 163 ...
Page 164: ...Drive module with options 0B051 0H371 IP00 UL Type Open 164 Dimension drawings ...
Page 165: ...Mounting plate opening 3AXD50000038119 Dimension drawings 165 ...
Page 166: ...3AXD50000038119 166 Dimension drawings ...
Page 167: ...External control unit 3AXD50000011687 Dimension drawings 167 ...
Page 168: ...168 ...