Additional grounding requirements – IEC
This section gives grounding requirements according to standard IEC/EN 61800-5-1.
Because the normal touch current of the drive is more than 3.5 mA AC or 10 mA DC:
•
the minimum size of the protective earth conductor must comply with the local
safety regulations for high protective earth conductor current equipment, and
•
you must use one of these connection methods:
1.
a fixed connection and:
•
a protective earth conductor with a minimum cross-sectional area of
10 mm
2
Cu or 16 mm
2
Al (as an alternative when aluminum cables are
permitted),
or
•
a second protective earth conductor of the same cross-sectional area as
the original protective earth conductor,
or
•
a device that automatically disconnects the supply if the protective earth
conductor is damaged.
2.
a connection with an industrial connector according to IEC 60309 and a
minimum protective earth conductor cross-section of 2.5 mm
2
as part of a
multi-conductor power cable. Sufficient strain relief must be provided.
If the protective earth conductor is routed through a plug and socket, or similar means
of disconnection, it must not be possible to disconnect it unless power is
simultaneously removed.
Note: You can use power cable shields as grounding conductors only when their
conductivity is sufficient.
■
Additional grounding requirements – UL (NEC)
This section gives grounding requirements according to standard UL 61800-5-1.
The protective earth conductor must be sized as specified in Article 250.122 and table
250.122 of the National Electric Code, ANSI/NFPA 70.
For cord-connected equipment, it must not be possible to disconnect the protective
earth conductor before power is removed.
Selecting the control cables
■
Shielding
Only use shielded control cables.
Use a double-shielded twisted pair cable for analog signals. ABB recommends this
type of cable also for the pulse encoder signals. Use one individually shielded pair for
each signal. Do not use common return for different analog signals.
70 Guidelines for planning the electrical installation
Summary of Contents for ACS880-04F-504A-3
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 04F drive modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 26: ...26 ...
Page 36: ...36 ...
Page 44: ...44 ...
Page 50: ...50 Mechanical installation ...
Page 56: ...56 ...
Page 116: ...116 ...
Page 122: ...4 3 2 122 Maintenance ...
Page 128: ...128 ...
Page 143: ... Package dimensions Package dimensions without IP shroud kit Technical data 143 ...
Page 158: ...158 ...
Page 160: ...Standard configuration IP20 UL Type Open 160 Dimension drawings ...
Page 161: ...Drive module with options E208 and H370 IP20 UL Type Open Dimension drawings 161 ...
Page 162: ...Drive module with options 0B051 E208 0H371 IP00 UL Type Open 162 Dimension drawings ...
Page 163: ...Drive module with options 0B051 E208 0H371 C217 IP00 UL Type Open Dimension drawings 163 ...
Page 164: ...Drive module with options 0B051 0H371 IP00 UL Type Open 164 Dimension drawings ...
Page 165: ...Mounting plate opening 3AXD50000038119 Dimension drawings 165 ...
Page 166: ...3AXD50000038119 166 Dimension drawings ...
Page 167: ...External control unit 3AXD50000011687 Dimension drawings 167 ...
Page 168: ...168 ...