![ABB ACS880-01 Series Firmware Instructions Download Page 473](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621473.webp)
Parameters 473
(Only visible when IGBT supply unit control activated by
Defines the DC voltage reference for the supply unit when
is set to
0.0 V
0.0 … 2000.0 V
User DC reference.
10 = 1 V
(Only visible when IGBT supply unit control activated by
Displays the reactive power reference sent to the supply unit.
This parameter is read-only.
-
-3276.8 … 3276.7
kvar
Reactive power reference sent to the supply unit.
10 = 1 kvar
(Only visible when IGBT supply unit control activated by
Selects the source of the reactive power reference to be sent
to the supply unit.
Zero
None.
0
User ref
1
). -
(Only visible when IGBT supply unit control activated by
Defines the reactive power reference for the supply unit when
is set to
.
0.0 kvar
-3276.8 … 3276.7
kvar
User reactive power reference.
10 = 1 kvar
95
Various hardware-related settings.
Selects the supply voltage range. This parameter is used by
the drive to determine the nominal voltage of the supply
network. The parameter also affects the current ratings and
the DC voltage control functions (trip and brake chopper
activation limits) of the drive.
WARNING!
An incorrect setting may cause the motor
to rush uncontrollably, or the brake chopper or resistor
to overload.
Note:
The selections shown depend on the hardware of the
drive. If only one voltage range is valid for the drive in
question, it is selected by default.
-
Not given
No voltage range selected. The drive will not start modulating
before a range is selected.
0
208…240 V
208…240 V
1
380…415 V
380…415 V
2
440…480 V
440…480 V
3
500 V
500 V
4
525…600 V
525…600 V
5
660…690 V
660…690 V
6
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...