![ABB ACS880-01 Series Firmware Instructions Download Page 447](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621447.webp)
Parameters 447
NULL
Zero
0
AI1 scaled
(see page
).
1
AI2 scaled
(see page
).
2
FBA1 ref
See parameter
(page
).
3
FBA2 ref
See parameter
(page
).
4
EFB1 ref
See parameter
(page
).
5
EFB2 ref
See parameter
(page
).
6
Aux input data 1
Value set in parameter
7
Aux input data 2
Value set in parameter
8
). -
Defines source 2 for signal that can be used as an input for
the pump curve function.
For parameter selections, see parameter
Defines Q-H pump curve frequency 1.
If there are several Q-H curves available from the pump
manufacturer, then set values for the fastest first.
0.00
0.00...600.00 Hz
Curve frequency in Hz.
10 = 1Hz
Defines Q-H pump curve frequency 2.
If there are several Q-H curves available from the pump
manufacturer, then set values for the fastest first.
0.00
0.00...600.00 Hz
Curve frequency in Hz.
10 = 1Hz
Defines Q-H pump curve frequency 3.
If there are several Q-H curves available from the pump
manufacturer, then set values for the fastest first.
0.00
0.00...600.00 Hz
Curve frequency in Hz.
10 = 1Hz
Defines Q-H pump curve frequency 4.
If there are several Q-H curves available from the pump
manufacturer, then set values for the fastest first.
0.00
0.00...600.00 Hz
Curve frequency in Hz.
10 = 1Hz
Defines Q-H pump curve frequency 5.
If there are several Q-H curves available from the pump
manufacturer, then set values for the fastest first.
0.00
0.00...600.00 Hz
Curve frequency in Hz.
10 = 1Hz
Defines scale coefficient for the Q-H pump curves.
Typically, the pump manufacturers specify Q-H curves valid
for water. Set the value corresponding to a specific gravity of
the pumped fluid.
1.000
0.000...30.000
Pump curve scale coef.
1000 = 1
Defines curve 1 maximum Head value at the corresponding
Flow value of 0.
0.00
0.00...32000.00
Head at 0 flowrate 1.
10 = 1
Defines curve 1 maximum Flow value at the corresponding
Head value of 0.
0.00
0.00...32000.00
Maximum flowrate.
10 = 1
Defines curve 1 Head value for the Downthrust limit.
0.00
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...