![ABB ACS880-01 Series Firmware Instructions Download Page 333](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621333.webp)
Parameters 333
…
configure a monitored start/stop
control logic for external equipment such as a contactor-
controlled motor cooling fan.
This parameter selects the signal that starts and stops the
fan.
0 = Stop
1 = Start
The output controlling the fan contactor is to be connected to
parameter
, bit 1. On and off delays can be set for the
fan by
respectively. A feedback signal
from the fan can be connected to an input selected by
;
the loss of the feedback will optionally trigger a warning or
fault (see
b6
b6)
Off
0 (function disabled).
0
On
1.
1
Running
Bit 6 of
2
). -
Defines a start delay for the motor fan.
The delay timer starts when the control source selected by
parameter
switches on. After the delay, bit 1 of
switches on.
0 s
0…42949673 s
Motor fan start delay.
1 = 1 s
Defines a stop delay for the motor fan.
The delay timer starts when the control source selected by
parameter
switches off. After the delay, bit 1 of
switches off.
20 min
0…715828 min
Motor fan stop delay.
1 = 1 min
Selects the input for motor fan feedback signal.
0 = Stopped
1 = Running
After the fan is started (bit 1 of
switches on), feedback
is expected within the time set by
;
b6)
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
DIO1
Digital input/output DIO1 (
, bit 0).
10
DIO2
Digital input/output DIO2 (
, bit 1).
11
). -
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...