Parameters 327
Selects the source from which measured temperature 2 is
read.
For wiring examples, see the hardware manual of the drive.
Usually this source is from a sensor connected to the motor
controlled by the drive, but it could be used to measure and
monitor a temperature from other parts of the process as long
as a suitable sensor is used as per the selection list.
Disabled
None. Temperature monitoring function 2 is disabled.
0
Estimated
temperature
Estimated motor temperature (see parameter
).
The temperature is estimated from an internal drive
calculation. It is important to set up the ambient temperature
of the motor in
1
KTY84 analog I/O
KTY84 sensor connected to the analog input selected by
parameter
and an analog
output. The input and output can be on the drive control unit
or on an extension module.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to
U
(voltage). Any change must be validated by a
control unit reboot.
• Set the unit selection parameter of the input to volt.
• Set the source selection parameter of the analog output to
“
• Select the analog input in parameter
. In case the
input is located on an I/O extension module, use the
selection
to point at the actual input value parameter
(for example,
The analog output feeds a constant current through the
sensor. As the resistance of the sensor changes along with its
temperature, the voltage over the sensor changes. The
voltage is read by the analog input and converted into
degrees.
2
KTY84 encoder
module 1
KTY84 sensor connected to encoder interface 1.
See also parameters
3
KTY84 encoder
module 2
KTY84 sensor connected to encoder interface 2.
See also parameters
4
1 × Pt100 analog
I/O
Pt100 sensor connected to a standard analog input selected
by parameter
output. The input and output can be on the drive control unit
or on an extension module.
The required settings are the same as with selection
, except that the source selection parameter of the
analog output must be set to
5
2 × Pt100 analog
I/O
As selection
, but with two sensors
connected in series. Using multiple sensors improves
measurement accuracy significantly.
6
3 × Pt100 analog
I/O
As selection
, but with three sensors
connected in series. Using multiple sensors improves
measurement accuracy significantly.
7
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...