![ABB ACS880-01 Series Firmware Instructions Download Page 306](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621306.webp)
306 Parameters
Selects which indications are given when one or both Safe
torque off (STO) signals are switched off or lost. The
indications also depend on whether the drive is running or
stopped when this occurs.
The tables at each selection below show the indications
generated with that particular setting.
Notes:
• This parameter does not affect the operation of the STO
function itself. The STO function will operate regardless of
the setting of this parameter: a running drive will stop upon
removal of one or both STO signals, and will not start until
both STO signals are restored and all faults reset.
• The loss of only one STO signal always generates a fault
as it is interpreted as a malfunction.
For more information on the STO, see the
Hardware manual
of the drive.
Fault/Fault
0
Fault/Warning
1
No.
Name/Value
Description
Def
/
FbEq16
Inputs
Indication (running or stopped)
IN1
IN2
0
0
0
1
Faults
1
0
Faults
1
1
(Normal operation)
Inputs
Indication
IN1
IN2
Running
Stopped
0
0
Fault
Warning
0
1
Warning
and fault
1
0
Warning
and fault
1
1
(Normal operation)
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...