![ABB ACS880-01 Series Firmware Instructions Download Page 269](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621269.webp)
Parameters 269
Defines the proportional gain (K
p
) of the speed controller. Too
high a gain may cause speed oscillation. The figure below
shows the speed controller output after an error step when
the error remains constant.
10.00;
5.00
(
b1/b2)
If gain is set to 1.00, a 10% error (reference - actual value) in
the motor synchronous speed produces a proportional term of
10%.
Note:
This parameter is automatically set by the speed
controller autotune function. See section
(page
).
0.00 …250.00
Proportional gain for speed controller.
100 = 1
No.
Name/Value
Description
Def
/
FbEq16
Gain = K
p
= 1
T
I
= Integration time = 0
T
D
= Derivation time = 0
%
Controller
output = K
p
× e
Time
e = Error value
Controller output
E