198 Parameters
Selects the unit for readings and settings related to analog
input AI1.
Note:
This setting must match the corresponding hardware
setting on the drive control unit (see the hardware manual of
the drive). Control board reboot (either by cycling the power
or through parameter
) is required to
validate any changes in the hardware settings.
V
Volts.
2
mA
Milliamperes.
10
Defines the filter time constant for analog input AI1.
Note:
The signal is also filtered due to the signal interface
hardware (approximately 0.25 ms time constant). This cannot
be changed by any parameter.
0.100 s
0.000 … 30.000 s
Filter time constant.
1000 = 1 s
Defines the minimum site value for analog input AI1.
Set the value actually sent to the drive when the analog signal
from plant is wound to its minimum setting.
See also parameter
.
0.000 mA or
V
-22.000 … 22.000
mA or V
Minimum value of AI1.
1000 = 1 mA
or V
Defines the maximum site value for analog input AI1.
Set the value actually sent to the drive when the analog signal
from plant is wound to its maximum setting.
See also parameter
.
20.000 mA or
10.000 V
-22.000 … 22.000
mA or V
Maximum value of AI1.
1000 = 1 mA
or V
No.
Name/Value
Description
Def
/
FbEq16
63
%
100
T
t
O = I × (1 - e
-t
/T
)
I = filter input (step)
O = filter output
t
= time
T = filter time constant
Unfiltered signal
Filtered signal
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...