Drive/inverter module STO function and an FSO module
The table below lists the safety data for the Safe disconnection function, including the safety
data of the FSO module, the FSE-31 module (optional) and the safety data of worst case
ACS880 Safe torque off (STO). See section
One-channel or two-channel connection to an
.
Note:
•
The PFD values of the drive STO and the FSO and FSE-31 modules are based on T1
(proof test interval) of 2 or 5 years. The safety data and SIL capability are valid only
when proof testing is done with an interval of maximum 2 or 5 years.
•
The safety data in the table is valid only when parameter settings for the FSO digital
inputs are done according to section
in chapter
.
•
The FSE-31 module is included in the calculations only if a safety encoder is used in
the application, the FSO-21 module is configured to activate the SS1 function (stop
category 1) in overtemperature situations and the ramp monitoring method is used in
the SS1 function.
•
The safety integrity of the protection function must be verified as required in EN 50495.
The SIL capability of the drive/inverter module internal STO and the FSO and FSE-31
modules is up to SIL3 when parameter settings for the FSO digital inputs are done
according to section
in chapter
.
•
The PFD value defines the safety integrity for a low-demand application (demand rate
< 1/year) in respect to random failure rate.
•
The safety data below contains the failure rates (PFD) of the FSO and FSE-31 modules
and the drive internal STO.
Two-channel pulsed digital input
One-channel pulsed digital input
3
3
SIL capability
1.05E-08
1.10E-08
PFH (1/h, T
1
= 20 a)
8.57E-05
9.05E-05
PFD
avg
(T
1
= 2 a)
2.06E-04
2.17E-04
PFD
avg
(T
1
= 5 a)
> 99
> 99
SFF (%)
1
0
HFT
20
20
T
M
(a)
3AXD10000113948 F
Safety block diagrams
The safety block diagrams show the components that are included in the safety data
calculations. The temperature sensor(s) and protection relay(s) are not included in the
calculations.
36 Technical data
Summary of Contents for ACS880-01 Series
Page 2: ......
Page 4: ......
Page 39: ...ATEX certificate Technical data 39...
Page 40: ...40 Technical data...
Page 41: ...Technical data 41...
Page 42: ...Declaration of Conformity 42 Technical data...