Program features 69
Settings
Parameters
).
Other programmable protection functions
Five different event signals from the process can be connected to selectable inputs to
generate trips and warnings for the driven equipment. When the signal is lost, an
external event (fault, warning, or a mere log entry) is generated. The contents of the
messages can be edited on the control panel by selecting
Menu - Settings
-
Edit
texts
.
Motor phase loss detection (parameter
The parameter selects how the drive reacts whenever a motor phase loss is detected.
Earth (Ground) fault detection (parameter
)
The earth fault detection function is based on sum current measurement. Note that
• an earth fault in the supply cable does not activate the protection
• in a grounded supply, the protection activates within 2 milliseconds
• in an ungrounded supply, the supply capacitance must be 1 microfarad or more
• the capacitive currents caused by shielded motor cables up to 300 meters will not
activate the protection
• the protection is deactivated when the drive is stopped.
Drive interlocked detection (parameter
)
The drive monitors the status of the Drive interlocked input, and this parameter
selects which indications are given when the signals are lost. (The parameter does
not affect the operation of the Drive interlocked function itself). For more information
on the Drive interlocked function, see the
Hardware manual
.
Swapped supply and motor cabling (parameter
)
The drive can detect if the supply and motor cables have accidentally been swapped
(for example, if the supply is connected to the motor connection of the drive). The
parameter selects if a fault is generated or not. Note that the protection should be
disabled in drive/inverter hardware supplied from a common DC bus.
Stall protection (parameters
)
The drive protects the motor in a stall situation. It is possible to adjust the supervision
limits (current, frequency and time) and choose how the drive reacts to a motor stall
condition.
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...